95-8704
16
2.7
X3301 Reector Plates
X3301 models are supplied with either a black or
a stainless steel reflector plate. These plates are
not interchangeable. Order the replacement that
matches the reflector plate on your X3301 Flame
Detector.
PERIODIC CHECKOUT PROCEDURE
In compliance with SIL 2, a checkout of the
system using the Mag
o
i
or Man
o
i
feature
should be performed regularly to ensure that
the system is operating properly. Refer to Table
1 in the X3301 Safety manual, number 95-8720,
for frequency of proof tests. To test the system,
perform the “Fire Alarm Test” as described in the
“Startup Procedure” section of this manual.
CLOCK BATTERY
The real time clock has a backup battery that
will operate the clock with no external power.
Return the device to the factory for battery
replacement if needed.
NOTE
If the backup battery is depleted, there is no
effect on the operation of the ame detector,
but the time stamping of the data log may
be affected.
fEaTURES
• Long detection range to carbonaceous fires
• Unequaled false alarm rejection
• Responds to a fire in the presence of
modulated blackbody radiation (i.e., heaters,
ovens, turbines) without false alarm
• Microprocessor controlled heated optics for
increased resistance to moisture and ice
• Automatic, manual, or magnetic
o
i
testing
• Easily replaceable
o
i
plate
• Fire, fault, and auxiliary relays standard
• 0–20 mA isolated output (optional)
• Eagle Quantum Premier LON/SLC output
(optional)
• HART communication (optional)
• FDT/DTM capable
• Multiple sensitivity levels
• A tri-color LED on the detector faceplate
indicates normal condition and notifies
personnel of fire alarm or fault conditions
• Operates under adverse weather conditions
and in dirty environments
• Mounting arm allows easy sighting
• Integral wiring compartment for ease of
installation
• Explosion-proof/flame-proof detector housing.
Meets FM, CSA, ATEX Directive, and IECEx
certification requirements
• Class A wiring per NFPA-72
• Meets NFPA-33 response requirement for under
0.5 second (available when model selected)
• 5 year warranty
• RFI and EMC Directive compliant
Associated Manuals
List of X3301 related manuals:
TITLE FORM NUMBER
Pulse 95-8736
EQP 95-8533
SIL 2 (Safety) 95-8720
HART Addendum
95-8577
Hangar 95-8735
Q9033 Mounting Arm
and Collar Attachment
95-8686
Enhanced Flame Inspector
software for X-Series Flame
Detectors
95-8751
Q1130 Flange Mount 95-8662
Q1201 Laser Aimer 95-8404
Q1130 Flange Mount 95-8662
Q1116 Universal Air Shield 95-8597

Other manuals for Det-Tronics X3301