27
95-8704
2.7
FM Approval and Performance Report – Continued
T-Low Sensitivity
Fuel Size Distance feet (m) Average Response Time (seconds)***
n-Heptane
1 x 1 foot 50 (15.24)
<4
Methanol
1 x 1 foot
30 (9.14) 5
Methane
32 inch plume
30 (9.14) 3
Propane
32 inch plume
30 (9.14) 5
*** Add 2 seconds for EQP model
Low Sensitivity
Fuel Size Distance feet (m) Average Response Time (seconds)***
n-Heptane
1 x 1 foot 50 (15.24)
<10
Methanol
1 x 1 foot
30 (9.14) 10
Methane
32 inch plume
30 (9.14) 10
Propane
32 inch plume
30 (9.14) 9
*** Add 2 seconds for EQP model