29
95-8704
2.7
FM Approval and Performance Report – Continued
T-Low Sensitivity
False Alarm Source
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response Time
(seconds)***
Sunlight, direct, modulated, reflected* — 1 x 1 foot n-Heptane 15 (4.6) 8
Sunlight, direct, unmodulated, reflected* — 1 x 1 foot n-Heptane 35 (10.7) 9
Arc welding, modulated, #7014 8 (2.4) 1 x 1 foot n-Heptane 30 (9.1)
3
LED Lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 2
LED Lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 3
70 w sodium vapor, modulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 5
70 w sodium vapor, unmodulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 4
250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 5
250 w vapor lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 6
300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 6
300 w incandescent lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 4
500 w shielded quartz halogen lamp, modulated 10 (3.0) 1 x 1 foot n-Heptane
50 (15.24) 5
500 w shielded quartz halogen lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 5
1500 w electric radiant heater, modulated 10 (3.0) 1 x 1 foot n-Heptane
50 (15.24) 5
1500 w electric radiant heater, unmodulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 3
Two 34 w fluorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 6
Two 34 w fluorescent lamps, unmodulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 2
* Outdoor test conditions
*** Add 2 seconds for EQP model
Low Sensitivity
False Alarm Source
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response Time
(seconds)***
Sunlight, direct, modulated, reflected* — 1 x 1 foot n-Heptane 15 (4.6) 19
Sunlight, direct, unmodulated, reflected* — 1 x 1 foot n-Heptane 35 (10.7) 12
Arc welding, modulated, #7014 5 (1.5) 1 x 1 foot n-Heptane 30 (9.1)
10
LED Lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 9
LED Lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 12
70 w sodium vapor, modulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 11
250 w vapor lamp, modulated 5 (1.5) 1 x 1 foot n-Heptane
50 (15.24) 11
300 w incandescent lamp, modulated 5 (1.5) 1 x 1 foot n-Heptane
50 (15.24) 11
500 w shielded quartz halogen lamp, modulated 10 (3.0) 1 x 1 foot n-Heptane
50 (15.24) 10
500 w shielded quartz halogen lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 10
1500 w electric radiant heater, modulated 10 (3.0) 1 x 1 foot n-Heptane
50 (15.24) 12
1500 w electric radiant heater, unmodulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 8
Two 34 w fluorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane
50 (15.24) 10
* Outdoor test conditions
*** Add 2 seconds for EQP model