Dehum
Parameter Indications Comments
Dehum Ratio 80-90 % CFM in dehumidification
Active Low No , Yes If DH input is active-low
Fan
Parameter Indications Comments
Cont Fan Ratio 0-100, FC* % CFM when fan on
Rise 20-80, FC* Temperature rise (°F)
Autobackup
Parameter Indications Comments
Enabled No , Yes If autobackup is enabled
Wait Time 0-120, FC* Wait time before autobackup (min)
Update Delay 0-30, FC* Time before updating autobackup command (sec)
Set PT Offset 0.0-3.5, FC* Minimum offset with setpoint for autobackup (°F)
Rise 20-80, FC* Temperature rise (°F) for autobackup
System
Parameter Indications Comments
AC/HP ON Delay 005-120, FC* Fan delay after AC/HP start
AC/HP OFF Delay 005-240, FC* Fan delay after AC/HP stop
Ratio Max Pwr 20-100, FC* % of max. power of the furnace
Reset
Parameter Indications Comments
Factory Values No , Yes Reset furnace settings to factory defaults
* FC values will be shown if a more precise value has been configured at the furnace control (refer to the Supreme
furnace manual).
Alizé Heat Pump User Menus
Status
Parameter Indications Comments
Comp Speed XX Hz Compressor frequency
Fan Speed XXX RPM % Outdoor fan speed
Coil Temp XX dF % Indoor coil temperature (°F)
Tube Temp XX dF % Outdoor coil temperature (°F)
Comp Temp XX dF % Compressor discharge temperature (°F)
Version X_X_X Interface board firmware version
CFM/TON
Parameter Indications Comments
Heat CFM/TON 250-750 CFM/TON in heating
Cool CFM/TON 250-750 CFM/TON in cooling
Dry CFM/TON 250-750 CFM/TON in dehumidification
Defrost
Parameter Indications Comments
Defrost Fan % 0-100 % Fan during defrost
Defrost Heat No , Yes Use aux. heating during defrost.
If yes, the Defrost Fan % option will set the heat % of the furnace.
Reset
Parameter Indications Comments
Factory Values No , Yes Reset settings to factory defaults
26