EasyManuals Logo

DIG 400A Series User Manual

DIG 400A Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
21
SOLUTION: Verify that the controller does not show OFF in current time mode
CAUSE: AM/PM not set correctly in current time mode
SOLUTION: Check current time, change AM/PM if necessary
CAUSE: AM/PM not set correctly in start time mode
SOLUTION: Check start time(s), change AM/PM if necessary
CAUSE: Rain delay is preventing watering
SOLUTION: Set rain delay to off
CAUSE: Yellow sensor wires have been cut
SOLUTION: Re-connect sensor wires together with waterproof connector
CAUSE: Sensor is installed and is in a state that prevents watering
SOLUTION: Check sensor and wire splices and verify sensor is normally closed
PROBLEM: The display is blank
CAUSE: No buttons have been pushed in the previous 15 minutes
SOLUTION: Push any button
PROBLEM: Valve fails to close
CAUSE: Solenoid is loose
SOLUTION: Tighten solenoid by turning it clockwise to the right
CAUSE: Valve is installed backwards
SOLUTION: Check flow arrow and verify arrows points away from
water source – reverse valve if necessary
CAUSE: Debris is blocking solenoid port
SOLUTION: Shut off water supply, unscrew and remove solenoid, then open
water supply and flush out solenoid port, re-install solenoid
CAUSE: Flow control knob is too far open
SOLUTION: Turn flow control knob clockwise and retest
CAUSE: Drip System flow rate is below minimum flow rate
SOLUTION: Increase system flow rate by adding or changing drippers

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DIG 400A Series and is the answer not in the manual?

DIG 400A Series Specifications

General IconGeneral
BrandDIG
Model400A Series
CategoryController
LanguageEnglish

Related product manuals