24. Technical features
XC660D
Housing: Self extinguishing ABS.
Case: 4 DIN modules 70x135mm with male and female connectors; depth 60mm.
Mounting: DIN RAIL mounted in an omega (3) din rail.
Protection: IP20.
Connections: pluggable screw terminal block 2.5 mm
2
wiring.
Power supply: 230Vac ±10%. 50-60Hz, or 115Vac ±10%. 50-60Hz or 24Vac ±10%. 50-60Hz
Power absorption: 6VA max.
Display: 4 digits red led and 4 digit orange led.
Inputs: up to 4 NTC probes, or up to 3 4÷20mA or up to 0.5÷4.5Vdc transducer.
Digital inputs: up to 8 free voltage, 2 inputs main voltage
Relay outputs: 6 relay SPST, Rating according to the UL60730
Resistive 3A, 240VAC 50K cycles
Inductive (G.P.) 3A, 240VAC 30K cycles
Motor Load 240VAC, 1/8 hp (1.9FLA/11.4LRA), 30K cycles
Pilot Duty 180VA, 240VAC 30K cycles
Analogue output: 2 x 4÷20mA or 0÷10V, , SELV, Limited Energy circuit <15W
Serial output : RS485 standard Communication protocol: ModBus RTU
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B; Pollution grade: normal; Software class: A.
Operating temperature: -10÷60 °C.; Storage temperature: -25÷80 °C.
Relative humidity: 20
85% (no condensing)
Measuring range: NTC probe: -40÷110°C.
Resolution: 0,1 °C; 1°F; 0.1bar; 1 PSI;
Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
VC660 keyboard
Housing: self extinguishing ABS.
Case: facia 64x164 mm; depth 23mm
Mounting: panel mounting in a 56x72 mm panel cut-out with two screws.
3x2mm. Distance
between the holes 40mm
Protection: IP20; Frontal protection: IP65
Power supply: from XC660 power module, 12V, 100mA max, SELV, Limited Energy circuit
Display: : 4 digits red led and 4 digit orange led;
Optional output: buzzer
25. Parameters Default values
Label
Valori
Menù
Descrizione Parametri
Limiti
StC1
-10.0
Pr1
Set point for compressors
LSE÷HSE
StC2
-30.0
Pr1
Set point for compressors circit 2
2LSE÷2HSE
SEtF
35.0
Pr1
Set point for fans
LSF÷HSF
OA1
CPr1
Pr2
Load 1 configuration
nu - CPr1 - CPr2 - StP - dGS - 6dG -
dGSt - InC1 - InC2 - FAn - InF - LIn ALr
Liq - HGi
OA2
CPr1
Pr2
Load 2 configuration
nu - CPr1 - CPr2 - StP - dGS - 6dG -
dGSt - InC1 - InC2 - FAn - InF - LIn ALr
Liq - HGi
OA3
CPr1
Pr2
Load 3 configuration
nu - CPr1 - CPr2 - StP - dGS - 6dG -
dGSt - InC1 - InC2 - FAn - InF - LIn ALr
Liq - HGi