1592001850 XC660D GB r3.4 04.09.2017.docx XC660D 51/55
Label
Valori
Menù
Descrizione Parametri
Limiti
OA4
FAn
Pr2
Load 4 configuration
nu - CPr1 - CPr2 - StP - dGS - 6dG -
dGSt - InC1 - InC2 - FAn - InF - LIn ALr
Liq - HGi
OA5
FAn
Pr2
Load 5 configuration
nu - CPr1 - CPr2 - StP - dGS - 6dG -
dGSt - InC1 - InC2 - FAn - InF - LIn ALr
Liq - HGi
OA6
FAn
Pr2
Load 6 configuration
nu - CPr1 - CPr2 - StP - dGS - 6dG -
dGSt - InC1 - InC2 - FAn - InF - LIn ALr
Liq - HGi
CtyP
SPo
Pr2
Compressor type
SPo, dPo, Scr
StP
oP
Pr2
Valve output polarity
OP - CL
PC1
20
Pr2
Capacity of compressor 1
0÷100
PC2
20
Pr2
Capacity of compressor 2
0÷100
PC3
20
Pr2
Capacity of compressor 3
0÷100
PC4
20
Pr2
Capacity of compressor 4
0÷100
PC5
20
Pr2
Capacity of compressor 5
0÷100
PC6
20
Pr2
Capacity of compressor 6
0÷100
FtyP
404
Pr2
Refrigerant gas type
r22= R22; r134=134, r404=R404A; - 407A =
r407A; 407C= r407C; 407F= r407F; 410=
r410; 507=R507; CO2= CO2; r32 = r32; r290
= r290; r448 = r448A; r449 = r449A, r450 =
r450A, r513= r513; 1234 = r1234ze
Sty
yES
Pr2
Compressor Sequence type
no - yES
Rot
yES
Pr2
Fan Sequence type
no - yES
P1C
Cur
Pr2
P1 probe setting (4/20mA, 0-5V, ntc)
nP - Cur - tEn - ntc
PA04
-0.5
Pr2
4mA or 0.5V readout for P1 probe
(-1.0 ÷ PA20)BAR; (-15 ÷ PA20)PSI; (-100 ÷
PA20)KPA
PA20
11.0
Pr2
20mA or 4.5V readout for P1 probe
(PA04 ÷ 61.0)BAR; (PA04 ÷
885)PSI; (PA04 ÷ 6100)KPA
CAL
0.0
Pr2
P1 probe offset
-12.0÷12.0(°C); -20÷20 (°F); 12.0÷12.0
(bar); - 200÷200 (PSI) -999÷999 (kPA)
P2C
Cur
Pr2
P2 probe setting (4/20mA, 0-5V, ntc)
nP - Cur - tEn - ntc
FA04
0.0
Pr2
4mA or 0.5V readout for P2 probe
(-1.0 ÷ FA20)BAR; (-15 ÷ FA20)PSI; (-100 ÷
FA20)KPA
FA20
30.0
Pr2
20mA or 4.5V readout for P2 probe
(FA04 ÷ 61.0)BAR; (FA04 ÷
885)PSI; (FA04 ÷ 6100)KPA
FCAL
0.0
Pr2
P2 probe offset
-12.0÷12.0(°C); -20÷20 (°F); 12.0÷12.0
(bar);
- 200÷200 (PSI) -999÷999 (kPA)
P3C
nP
Pr2
P3 probe setting (4/20mA, 0-5V, ntc)
nP - Cur - tEn - nt10 - nt86
3P04
-0.5
Pr2
4mA or 0.5V readout for P3 probe
(-1.0 ÷ FA20)BAR; (-15 ÷ FA20)PSI; (-100 ÷
FA20)KPA
3P20
11.0
Pr2
20mA or 4.5V readout for P3 probe
(3P04 ÷ 61.0)BAR; (3P04 ÷
885)PSI; (3P04 ÷ 6100)KPA
O3
0.0
Pr2
P3 probe offset
-12.0÷12.0(°C); -20÷20 (°F); 12.0÷12.0
(bar);
- 200÷200 (PSI) -999÷999 (kPA)
P4C
nP
Pr2
P4 probe setting (NTC 10K, NTC 86K)
nP - nt10 - nt86
O4
0.0
Pr2
P4 probe offset
-12.0÷12.0(°C); -20÷20 (°F)
2CPb
nP
Pr2
Probe selection for second suction
circuit
nP - P1 - P2 - P3
FPb
P2
Pr2
Probe setting for fan
nP - P1 - P2 - P3
iF01
oA1
Pr2
Configurable digital input 1 function
(terminals 13-14)
nu - OA1- OA2 - OA3 - OA4 - OA5 - OA6 -
InF - LP1 - LP2 - HP - ES - OFF - LL - SIL
EAL Co1 Co2 Co3 Co4 Co5 Co6