Smart Touch Cabin Control Installation & Operations Manual MODES OF OPERATION
L-3380 ENGLISH 27
MAIN MENU PROGRAMMABLE PARAMETERS
Table 1: Main Menu – Programmable Parameters
Main
Category
Item Sub Item 1 Sub Item 2 Sub Item 3
Range
(min/max) or
Choices Factory Default
HVAC Control
Settings
Page 1
General Settings Page 1
High Fan Speed 35 95 95
Medium Fan Speed 32 85 61
Low Fan Speed 30 75 50
Page 2
Inside Temp Calibration ±50°F or ±25°C 0
Temperature Units
(°F/°C) Auto/°F/°C Auto
Reversed Fan Speed in
Heat
Off/On On
Page 3
Electric Heat or Auxiliary
Heat Option
Off / Elec / Aux Elec Heat Off
Fan Motor Type Shade-Pole/Split-Capacitor Split-Capacitor
Filter Hours Setting Off/100-2500 Hours Off
Page 4
Filter Hours Reset Clear only n/a
CAN Bus Unit ID 1 255 n/a
CAN Bus Group ID 1 255 n/a
Page 5
Voltmeter Calibration 70-140V AC or 170-260V AC 0 (none)
Set Point Temp Differential 1 or 2°F / 0.5 or 1.0°C 2°F/1°C
Humidity Mode Min Temp 40°F/5°C 75°F/25°C 50°F/10°C
Page 6
Auto Fan Speed Temp
Differential
1-3°F or 0.5-1.5°C 2°F/1°C
Supply Air Temp Limit Off/95-140°F or Off/35-60°C Off
DX/CW Mode Selection Set by Jumper / DX Override / CW
Override
Set by Jumper
Page 7
Inside Temp Sensor
Selection
Auto / Display / Alt. Air Auto
Fan Operational Mode Continuous or Cycled Continuous
Dual Temp Set Points Off/On Off
Page 8
Humidity Sensor Limit [50%-80%] 60%