6.1 Circuit Board Settings and Descriptions
SECTION 6 - OPTIONAL CONVENIENCE OPEN SYSTEM
The optional convenience open system installed in your vehicular gate operator is designed as a convenience enhancement only.
It is not designed or intended to provide continuous gate operation during a power outage. Its sole purpose is to provide a
method to open the vehicular gate to allow unimpeded traffic flow when the gate and access control system is without power. If
your access control system requires 100% power backup and continuous operation when primary (AC) power has failed, a
power inverter / backup system, such as DoorKing’s Model 1000 is required.
• The convenience open system cannot provide continuous gate operation during a power outage.
•
This system cycles the arm to the open position one time only after AC power failure.
• The convenience open system requires testing on a monthly basis to insure the batteries are fully charged and that the
system is operational.
• The convenience open system uses two 12-volt, 3.0 amp-hour gel-cell batteries. These batteries should be replaced
every two years on average, or sooner if required.
• Batteries are affected by temperature. Cold temperatures will reduce the effectiveness of the batteries. High temperatures
will result in a shortened battery life.
• Batteries are not covered under warranty.
This convenience open system consist of a control board (1473-010), motor and power supply (batteries) providing a
completely redundant drive system to open the barrier arm should a power outage occur. This system is not designed to
maintain continuous barrier operation; rather it provides a convenient method to open the arm once during adverse conditions.
If continuous barrier and access control system operation is required, refer to the DoorKing Model 1000 Inverter / Backup
Power System.
Initial Power Up Convenience Open Note:
The DC power is not present on the main
circuit board until the first initial cycle.
ON
1234
12345678910
115 VAC
INPUT
J1
P1
RESET
CLEAR
STAT
AUTO OPEN
MOTOR DIR
AC ON ACT
LIMIT
TIMER
BATT STAT
RUN
TIME
HEART
BEAT
TRICKLE
CHARGE
STAT
SW2
ON
1473-010
DO NOT
use
Run Timer
DO NOT USE. Manual Mode.
Set so that the arm opens to the UP direction upon loss of AC power.
Auto Open
Operation
After Power
Outage
Motor Dir
Motor Direction
AC on ACT
Restore Power
Operation
Timer-OFF
Limit-ON
Operator Type
OFF
OFF
(Auto Mode) Apartment complexes, gated communities, etc.:
Arm will automatically raise to the operator’s UP limit position.
ON
Function Setting DescriptionSwitch
1
2
3
4
DO NOT USE. Physical Input Required.
OFF
DO NOT USE. “Run timer” is used and MUST be adjusted.
Timer-OFF
Auto: a 1-second pulse is automatically sent to the barrier gate
operator input to restore normal operation again.
ON
Operator limits are used to stop arm at UP position.Limit-ON
DIP-Switches
HEART BEAT LED
Blinking:Indicates board is operating normally.
Reset Button
Press to reset board.
Beeper
A beep every 20 seconds indicates that battery
replacement is needed. Press and hold the
CLEAR STAT button to reset the battery reminder
beeper and clear the counter. LEDs will also
indicate battery status.
Clear Stat Button
Press and hold the CLEAR STAT button for 4 secs
clears the battery replacement reminder counter
and resets the beeper. LEDs will also indicate
battery status.
Battery LEDs
BATT STAT LED
2 Blinks: Replace batteries.
3 Blinks: Battery level is too low.
4 Blinks: Batteries are not connected.
5 Blinks: Bad battery.
6 Blinks: Battery charge current exceeds maximum,
possible shorted cell.
TRICKLE LED
Steady Green LED: Battery is fully charged and a
trickle charge is being used to maintain a full charge.
CHARGE LED
Steady Yellow LED: Battery is being bulk charged.
Blinking Yellow LED: Battery is 90% of a full charge.
STAT LED
3 Blinks: Extreme temperature, charging suspended.
1
1
2
2
3
3
4
Run Timer
DO NOT USE.
6
6
4
5
5
Operating Note: Arm will cycle to UP
position automatically (DIP-Switch 1
ON) during an AC power failure.
Operator’s DC limit sensor will stop
and hold the arm in the UP position
(DIP-Switch 4 ON). Operator will
automatically return to normal
operation once AC power has been
restored (DIP-Switch 3 ON).