XT SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Rapid-sorb and Ultra-sorb with Models XTP 050 through 096
Models XTP 050 through XTP 096 have capacities requiring dispersion devices with condensate drains (Figure 35-1).
For these models, DriSteem recommends the following:
Run separate steam tubing from each cylinder to the connection on the dispersion device.
Pitch steam tubing toward the dispersion device.
The installer should not attempt to drain condensate back to the cylinder. When a vertical riser is required in the steam
tubing, a drip tee is required in order to eliminate a condensate collection point that will restrict steam fl ow.
OM-7982-XT
Pitch*
Pitch*
Drain
Drain
Drip tee
Pitch*
Pitch*
Drain
Rapid-sorb steam dispersion panel
Ultra-sorb steam dispersion panel
Dual-cylinder XT Series humidifi er
WARNING
Preventing back pressure in dual-cylinder humidifi ers
Read and follow all steam tubing installation instructions
for dual-cylinder humidifi ers. Failure to follow these
instructions could result in excessive back pressure and
the risk of equipment damage or severe personal injury.
Notes:
* Pitch 1/8"/ft (1%) minimum toward dispersion panel.
See installation notes in Figure 25-1.
FIGURE 36-1: DUAL-CYLINDER XT SERIES HUMIDIFIER CONNECTED TO RAPID-SORB OR ULTRA-SORB WITH RISER DRIPS IN
STEAM SUPPLY LINES
INSTALLATION
Dispersion: