Electrode Steam Humidifier
Installation, Operation,
and Maintenance Manual
XT_IOM_Jan_2008.pdf 1 11/19/2009 10:13:30 AM

Questions and Answers

  • J
    jrhodesAug 19, 2025
    Why is my DriSteem Humidifier not filling with water?
    • T
      trantrevorAug 19, 2025
      Several factors can prevent your DriSteem Humidifier from filling with water. First, verify that the manual water supply valve is open and has pressure. Check if the water supply line strainer is plugged and clean or replace it if necessary. Also, ensure the fill valve electrical connections are secure. The unit control might not be on, so press the On/Off switch on the display panel and check the transformer electrical connections. The fill valve may be malfunctioning; cycle it in Service mode to see if it opens. If not, verify its electrical connections and check for 24 VAC (terminals 2 and 5). If voltage is present but the valve doesn't open, replace it. Finally, confirm the humidifier isn't in end-of-season drain mode by checking for a humidification demand signal at the control board.
  • R
    Robert WashingtonAug 23, 2025
    Why is my DriSteem XT-10 fill valve cycling on and off?
    • R
      Ronald ClarkeAug 25, 2025
      Frequent cycling of the fill valve in your DriSteem Humidifier often indicates a malfunctioning level control system or drain valve issues. Ensure water conductivity is at least 125 ?S/cm by adding sodium bicarbonate through the steam outlet. If the drain valve isn't fully closed due to an obstruction, clean the valve. Also, replace any broken or weak return spring on the drain valve.
  • R
    Rebecca LevineAug 26, 2025
    What causes my DriSteem Humidifier fill valve not to close?
    • R
      Ryan RayAug 26, 2025
      If the fill valve on your DriSteem Humidifier won't close, it could be due to a few reasons. A malfunctioning level control system could be the culprit, so ensure the high water sensor electrical plug is fully engaged. Check the water conductivity, which should be at least 125 ?S/cm; add sodium bicarbonate to increase it if needed. Another cause could be a stuck fill valve, so check for control voltage across the fill valve coil (terminals 2 and 5). Inspect for any obstructions preventing the valve from seating properly, and clean or replace the valve as necessary. Lastly, verify the drain valve is fully closed; clean or replace it if an obstruction prevents closure, or replace a broken or weak return spring.
  • M
    Maxwell HarrisAug 30, 2025
    What causes reduced output from my DriSteem Humidifier?
    • C
      Cody SteinAug 30, 2025
      Reduced or no output from your DriSteem Humidifier, even with the correct water level, can be caused by a malfunctioning control system or a steam cylinder issue. Check if auxiliary limit controls are preventing operation; reset, replace, or calibrate them as needed, or jumper H-H if they aren't used. Also, check the fuse in the power circuit and replace it if open. For the steam cylinder, verify that proper voltage is being applied and check the current through the electrode wires. If the power components aren't functioning, replace them.
  • T
    Tabitha GibsonSep 1, 2025
    What to do if my DriSteem XT-10 Humidifier does not perform the autodrain sequence?
    • G
      Gabrielle WilliamsSep 1, 2025
      If your DriSteem Humidifier isn't performing the autodrain sequence, start by verifying the drain valve electrical connections. Ensure 24 VAC is present at the internal controller board terminals 3 and 6 for the drain valve. Check the drain valve piping for any blockages. If voltage is present at the valve but it still doesn't open, replace the valve.
  • A
    Anthony Barnes DVMSep 4, 2025
    Why does my DriSteem XT-10 not perform end-of-season drain?
    • D
      Debbie JonesSep 4, 2025
      If your DriSteem Humidifier isn't performing the end-of-season drain, it could be due to a constant demand signal. Reduce the demand signal. Also, verify the drain valve electrical connections and ensure the drain valve is correctly wired to the control board. Check for 24 VAC across the valve coil during the test cycle (terminals 3 and 6).
  • M
    meadowsmichaelSep 6, 2025
    Why is humidity above the set point with my DriSteem XT-10 Humidifier?
    • T
      Tonya BellSep 6, 2025
      If the humidity is consistently above the set point with your DriSteem Humidifier, several factors could be at play. The humidistat might be improperly located. Reduced airflow could also be a factor, so check the fans and dampers. Malfunctioning controls could be another cause; check for incorrect supply voltage, control signal, and wiring. If the humidity controller is out of calibration, repair or recalibrate it. Also, check if the contactor is shorted and repair or replace as needed. The unit might be oversized, so reduce the output limit (OL) setting. Finally, high entering relative humidity could be the issue, so consider dehumidifying.
  • M
    maxwellgordonSep 8, 2025
    Why is my DriSteem Humidifier display blank?
    • K
      Kayla GreeneSep 8, 2025
      A blank display on your DriSteem Humidifier usually indicates a power issue or a connection problem. First, check the main power supply and reset the control transformer circuit breaker if it has tripped. If the modular communication cable is disconnected, connect it.
  • M
    Margaret MortonSep 12, 2025
    Why is my DriSteem Humidifier hunting?
    • J
      jeffreygreeneSep 12, 2025
      Hunting, or humidity swings above and below the desired set point, in your DriSteem Humidifier often indicates a malfunctioning control system. If the humidity controller is faulty or inaccurate, repair or replace it. Also, relocate any poorly located control components.
  • H
    hughesscottSep 13, 2025
    Why is my DriSteem XT-10 making noise?
    • E
      Erika MatthewsSep 13, 2025
      Noisy operation in a DriSteem Humidifier can stem from contactor or fill valve issues. For contactor noise, verify the electrical connections of the contactor and transformer, and check for 24 VAC on the internal control board terminal strip. A continuous chattering noise indicates a failing contactor or malfunctioning controls, so replace the contactor or troubleshoot the control system. For fill valve noise, a clicking or hissing sound is normal, but a slamming sound indicates "water hammer," which can be minimized by installing a shock arrestor. A loud buzzing sound suggests poor alignment or valve stem issues, so replace the valve.

DriSteem XT-10 Specifications

General IconGeneral
ModelXT-10
Water Connection1/2" NPT
Drain Connection1/2" NPT
TypeElectric Steam Humidifier
Humidification CapacityUp to 20 lbs/hr (9.1 kg/hr)
Steam OutputUp to 20 lbs/hr (9.1 kg/hr)