43
[25] Sixth System Option Code
Page 26
Default Zone Light ON Zone Light OFF
OFF Zone Light 1 Force Arming on Zone Types No Force Arming
0, 1, 2 and 3
ON Zone Light 2 Entry/Exit sounder enabled Entry/Exit sounder disabled
OFF Zone Light 3 Arming Inhibit enabled Arming Inhibit disabled
OFF Zone Light 4 PC16OUT Module on PO1 enabled PC16OUT Module disabled
OFF Zone Light 5 Bell Always on Tamper 24-Hour Bell/Buzzer on Tamper
OFF Zone Light 6 Installer Tamper Reset Tamper follows restore
OFF Zone Light 7 Tamper Zone 8 enabled Tamper Zone 8 disabled
OFF Zone Light 8 Engineer Reset enabled Engineer Reset disabled
[26] Seventh System Option Code
Page 27
Default Zone Light ON Zone Light OFF
OFF Zone Light 1 Zone 7: Fire Zone
t
Zone 7: Normal Zone
OFF Zone Light 2
Not Used
OFF Zone Light 3 2-minute keypad timeout No keypad timeout
OFF Zone Light 4 Keypad Tamper Enabled Keypad Tamper Disabled
OFF Zone Light 5 Battery test every 10s Battery test every 4 minutes
OFF Zone Light 6 AC Trouble Not Reported AC Trouble Reported
OFF Zone Light 7 AC supply: 60Hz AC supply: 50Hz
OFF Zone Light 8
Not Used
t
When Zone Light 1 is ON, the Zone Definition programmed in Section [18] for Zone 7 will be ignored.
[27] Maximum Dialing Attempts per Buffer
Page 27
Default
0 3 Communications Buffer 1
0 3 Communications Buffer 2
0 3 Downloading Telephone Number
[28] Swinger Shutdown and Transmission Delay/Bell Delay
Page 28
Default
0 3 Swinger Shutdown
0 0 Transmission Delay (seconds)
0 0 Bell Delay (minutes)
PC2585 Version
1.1R
Swinger Shutdown: Enter a number from “01” to “99”;
“00” provides unlimited transmissions per zone. Note
that the Fire Zone will always transmit.
Transmission Delay / Bell Delay: The Transmission
Delay is counted in seconds; the Bell Delay is counted
in minutes.
The Transmission and Bell Delays are applied to
Burglary Zones only.