Program Descriptions: 5.32 Walk Test (Installer)
27
1. The panel is disarmed
2. The Keypad Blanking option is disabled (section [016]:
[3])
3. The Fire Bell is Continuous option is disabled (section
[014]: [8])
4. The Transmission Delay is disabled, if Transmission
Delay is not required (section [370])
NOTE: Fire Troubles are not supported in Walk Test.
To perform a Walk Test:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
When any zone is violated the panel will activate the Bell Out-
put for two seconds, log the event to the event buffer and
communicate the alarm to central station. Each zone should
be tested several times during the test. Check the event buffer
to ensure that all zones and FAP keys are functioning properly.
To stop the test:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
Check the event buffer after the Walk Test is complete, to
ensure that the Audible/Silent 24-hr PGM alarms have been
restored.
NOTE: The Alarm Memory is cleared upon entering Walk Test
mode. Zones that were violated during the Walk Test will be
stored as alarms in alarm memory. The Memory light will turn
off the next time the panel is armed.
Installer Walk Test Enable/Disable . . . . . . . . . . Section [901]