EasyManua.ls Logo

DSC T-Link TL300 - Standard Installation (Mode 4)

DSC T-Link TL300
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
Section 5: Standard Installation (Mode 4, TL250 only)
5.1 PC1616/1832/1864, Power864, and Maxsys Panel Setup and
Installation
Refer to the control panel Installation Manuals for detailed installation instructions. Mount the
T-Link on the side wall of the PC4050C or PC4050CR cabinet. Refer to Appendix C for Net-
work Protection installation instructions.
Remove power from the control panel before any connections are made to the T-Link TL250.
Connect the + and - terminals to the panel auxiliary power output. Connect the supplied cable
from the T-Link TL250 white connector to the PC-Link header of the control panel.
The black wire of the PC-Link cable is pin 1 (facing the right side of the board) on the PC-Link
header for the PC5020 v3.2 or higher and PC1616/1832/1864 v4.1 or higher control panels.
The PC-Link header is polarized on the PC4020 v3.31 or higher control panel. Connect the e-
ground to a proper earth-ground connection.
5.2 Standard Connection with PC1616/1832/1864/PC4020(CF)/PC5020(CF)
NOTE: All circuits are supervised and power limited. Refer to section 5.4, UL Listed Commercial Fire Sys-
tems diagram for wire routing. Do NOT route any wiring over the circuit boards. Maintain at least 1”
(25.4mm) separation between circuit board and wiring.
A minimum of 1/4” (7mm) separation must be maintained at all points between non-power lim-
ited wiring and power limited wiring.
12-24Vdc
TX RX GND RED BLK YEL GRN PGM1PGM2 IN1 GND IN2 IN3 GND IN4 EARTH
Network
PC-LINK
PC-LINK
SUPERVISED
SUPERVISED
STAT
Network Connection
Use only CAT5 cable
(300ft / 100m max.)
Supervised
WARNING!: Do not connect transformer
to receptacle controlled by a switch. The
transformer must be UL Listed and have
a restraining means.
V = 12VDC
I = 250mA (275mA with PGM or PC5108)
RED
BLK
+
-
LK
ACT
SPD
16.0V@40VA
NOTE: The black wire is on
the right side and red wire is
on the left.
Recommended: DSC PTD 1640U-CC
DG009338
+
-
NOTE: For ULC Central Station
Fire and Burglary Monitoring con-
figurations please refer to ULC
Installation Sheet part #29002157.

Related product manuals