EasyManua.ls Logo

DST RL-61 - 9 Troubleshooting; Error Codes; General Troubleshooting; FIGURE 20: Troubleshooting Table and Solution

DST RL-61
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
RL-61, 61L EN.033 24.01 Seibu Giken DST
EN
9 TROUBLESHOOTING
9.1 ERROR CODES
The dehumidier will automatically shut down if an error is detected. During shut down, a timed cooling down period on the regeneration fan is initiated before turned o󰀨. See
below for error codes.
CODE EXPLANATION CAUSE SOLUTION
If the unit stops and
the ALARM-light is lit.
Process fan overloaded.
Regeneration fan
overloaded.
Excessive airow.
Short-circuit or fan malfunction.
Check fan.
Check setpoint of F1/F2 or Q1/Q2.
Reset F1/Q1 or F2/Q2 check and adjust airow.
Have a qualied electrical technician to investigate.
Regeneration air thermostat
TH1 has tripped.
Regeneration heater
overloaded.
Note: Not applicable when
tted with steam.
TH1 setting incorrect.
TH1 defective (fail safe).
Incorrect shut down.
Insu󰀩cient regeneration airow.
Excessive regeneration heater power.
Regeneration heater malfunction.
Check TH1 setting.
Check correct operation of TH1.
Reset TH1 - reset F3 - F5.
Check regeneration airow and fan operation.
Check TH2 setting.
Check and replace heater.
Overload in the transformer. Short-circuit or transformer malfunction. Check transformer.
Wet air thermostat tripped
(TH3).
TH3 setting incorrect.
Excessive regeneration airow.
Excessive regeneration heater power .
Incorrect or intermittent rotor rotation.
Insu󰀩cient system moisture load.
Check TH3 setting.
Check and adjust regeneration airow.
Check TH2 setting.
Check rotor drive system.
Check process airow and fan operation.
Check process inlet moisture content.
Check RH controller setpoint/output control signal.
Rotation guard sensor has
not detected movement
(KA13).
Rotor drive system failure.
Sensor failure or incorrect clearance.
Check drive motor & transmission (correct belt tension).
Check clearance gap between sensor and rotor marker.
Turn the [0/1]-switch to “0”-position and main switch to “0/
OFF”-position to restore.
Frequency converter alarm.
Note: Option
Frequency converter internal alarm activated Refer to converter manual for fault code explanation.
EMERGENCY
STOP BUTTON is lit.
Operation terminated.
Emergency button activated.
[0/1]-switch is active (if tted with auto restart).
Pull the emergency button to restore.
Turn the [0/1]-switch to “0”-position to restore.
The unit is running
and the ALARM ΔP-
light is lit .
Note: Applicable for
RL-61/71 only.
Internal pressure balance is
not optimal.
The negative pressure on the regeneration air
chamber is insu󰀩cient. See more information
on “4.3 Damper installation”.
Throttle the damper on regeneration air in or dry air out until
ALARM ΔP-light is turned o󰀨.
Reduce the pressure fall by changing the process inlet lter
more frequently.
Check the airow guard.
Check the airow guard setting (recommended is 30Pa).
Note: Top panel must be mounted during testing to avoid
triggering the ALARM ΔP.
FIGURE 20: Troubleshooting table and solution
9.2 GENERAL TROUBLESHOOTING
Check for following if the unit will not start-up.
PROBLEM CAUSE SOLUTION
Unit will not start. None of the light
indicators are on.
No power to unit.
No power to control circuit.
The emergency stop button is
active.
Conrm electric supply and check local isolator is on.
Check remote control is set to ‘On/Run’ position.
Check all circuit breakers are set to ‘Start/On’ position.
Pull the emergency stop button and then turn the operating switch to “0” .
The ALARM-light is on but the unit will
not start.
Alarm circuit is preventing
start-up.
Check TH1 & TH3 thermostats are set.
Check all circuit breakers are set to ‘Start/On’ position.
Check fan motor overloads are set to ‘Start/On’ position.
The dehumidier is turned on but does
not appear to be operating.
A circuit is preventing
operation.
Operation can be checked by lowering control setpoint or switching to ‘manual’ operation.
Check remote control is set to ‘On/Run’ position and if the cable is undamaged.
Conrm electric supply and check local isolator is on.
FIGURE 21: General troubleshooting table and solution

Table of Contents

Related product manuals