EasyManuals Logo

Dungs MPA22 User Manual

Dungs MPA22
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
Printed in Germany / M-MT-BOS
Edition11.99 # 231 763
19 … 112
Operating mode
Oil firing, three stage
If no flame is present after the startup safety period has elapsed, the burner
enters the non-variable fault state.
If flame failure occurs while the burner is operating, a fault shut-down takes
place and the system executes a restart. If the presence of a flame is not
signalled, the system enters the non-variable fault state.
In the event of a fault shut-down, all valves are closed and the blower and
ignition are turned off.
If the presence of a flame is signalled before the gas is enabled, the automatic
burner control enters the non-variable fault state.
The type of fault or disturbance is displayed.
If air pressure switch failure is detected during the startup period, provided the
watchdog function is activated, a safety shut-down takes place and 5 restart
attempts are performed; if this occurs when the burner is operating, the
automatic burner control enters the non-variable fault state.
If the oil pressure drops, the automatic burner control enters the non-variable
fault state.
Response to faults
Oil firing, three stage

Table of Contents

Other manuals for Dungs MPA22

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dungs MPA22 and is the answer not in the manual?

Dungs MPA22 Specifications

General IconGeneral
BrandDungs
ModelMPA22
CategoryController
LanguageEnglish

Related product manuals