Printed in Germany / M-MT-BOS
• Edition 11.99 • # 231 763
38 … 112
Setup mode
Gas firing, electronic
modulation
The controller automatically goes to standby status if the automatic burner-
control system has not been programmed. In the unprogrammed state, the
automatic burner-control system remains on standby. Unprogrammed means
that the characteristic has not been fully programmed.
Once a valid characteristic has been programmed and the automatic burner-
control system detects the presence of the corresponding components when
it starts up, the burner starts as soon as the control chain and GWmax
are
closed.
If you want to correct a characteristic or ignition point P0 without recalculating
all other points as well, you can access setup mode by simultaneously pressing
the "+" and "-" buttons.
Simultaneously press the "1" and "2" buttons if you want to enter the full setup
mode. The "P" symbol always appears in the display to indicate that setup
mode is activated. If you do not press a button in setup mode before the
timeout expires, setup mode is exited automatically and a RESTART is
performed.
■ The burner must be in standby
status, otherwise you cannot
access the setup mode
■ Changing a characteristic de-
fined beforehand
■ Accessing setup mode