Table 4
A82/E82
Flame failure ( more than 3 flame
failures in 4 minutes)
Flame detecon problem
E83 Ignion circuit error Flame detecon problem
If the flame detecon error is
repeated more than 3 mes in a
row without reaching the
operang mode, this error is set.
A88/E88 Flame Detecon Error
Even if it reaches the operang
mode, if the flame detecon error
is repeated more than 3 mes
within 24 hours, it will switch to
this error.
A89/E89 Flame Detecon Error
C07/F07
Over Temperature Error for Flue
Gas
It occurs when the temperature of
the flue gas exceeds 95°C.
Nofy authorized service of E.C.A.
Problem on ionizaon circuit
1
2
-
-
Press reset buon.
C08/F08 Ionizaon component error
components
If the error is sll present (or persists) aer reset,
nofy authorized service of E.C.A.
C13/F13 Repeated Reset Failure
Pressing of Reset buon more
than 5 mes in an hour
Nofy authorized service of E.C.A.
C22/F22 Gas valve circuit error
Problem on gas valve circuit
components
It occurs when water pressure
sensor detects a relavely low
water pressure (0.4 bar) for your
device.
C37/F37 Low Water Pressure Fault
reaches 1.5-2 bar (device will eliminate error when
the pressure is over 0,8 bar).
1- Press reset buon.
C39/F39 Outer Air Sensor Fault
Outer air sensor might be
defecve.
2- If the error is sll present (or persists) aer reset,
nofy authorized service of E.C.A.
It occurs when water pressure
sensor detects a relavely high
water pressure (3,3 ±0,3 bar) for
your device.
C40/F40 High Water Pressure Fault
C41/F41 Filling Error Autofill Problem
C42/F42
Filling could not be completed
error
The problem of filling not being
completed within the expected
me
C43/F43
Low Pressure Error (In Case of
Filling Lockout)
Low pressure repeat problem
C47/F47 Water Pressure Sensor Error
Water pressure sensor is not
plugged in or there is no contact.
C50/F50 Boiler Sensor Fault Boiler sensor might be defecve.
C51/F51 PT1000 Solar Sensor Error
PT1000 solar sensor might be
defecve.
C52/F52
Error on temperature sensor for
domesc water
Temperature sensor for domesc
water might be defecve.
Nofy authorized service of E.C.A.
C53/F53
Error on temperature sensor for
flue gas
The flue gas temperature sensor is
in short or open circuit state.
Nofy authorized service of E.C.A.
C81/F81
Temperature sensor deviaon
test delay
Temperature sensors might be
defecve.
Nofy authorized service of E.C.A.
1- Press reset buon.
2- If the error is sll present (or persists) aer reset,
nofy authorized service of E.C.A.
1- Press reset buon.
2- If the error is sll present (or persists) aer reset,
nofy authorized service of E.C.A.
1- Press reset buon.
2- If the error is sll present (or persists) aer reset,
nofy authorized service of E.C.A.
1- Press reset buon.
2- If the error is sll present (or persists) aer reset,
nofy authorized service of E.C.A.
1- Press reset buon.
2- If the error is sll present (or persists) aer reset,
nofy authorized service of E.C.A.
1- Check water pressure in heater installaon of
your device.
2- Fill the system with water unl the pressure
3- Check your valves and installaon against leaks.
4- If the problem is sll present (or persists), nofy
authorized service of E.C.A.
1- Check water pressure in heater installaon of
your device.
2- Turn off the device and restart it.
3- If the error is sll present (or persists) aer reset,
nofy authorized service of E.C.A.
1- Press reset buon.
2- If the error is sll present (or persists) aer reset,
nofy authorized service of E.C.A.
1- Press reset buon.
2- If the error is sll present (or persists) aer reset,
nofy authorized service of E.C.A.
1- Press reset buon.
2- If the error is sll present (or persists) aer reset,
nofy authorized service of E.C.A.
1- Press reset buon.
2- If the error is sll present (or persists) aerreset,
nofy authorized service of E.C.A.
1- Press reset buon.
2- If the error is sll present (or persists) aerreset,
nofy authorized service of E.C.A.
1- Press reset buon.
2- If the error is sll present (or persists) aerreset,
nofy authorized service of E.C.A.