INPUT ISOLATION TRANSFORMER INSTALLATION
Eaton 9155 UPS (8–15 kVA) User's Guide S 164201553 Rev G (www.eaton.com/powerquality)
21
17. Hardwire the input terminations (TB1‐1 through TB1‐3) for the input isolation
transformer.
See Table 2 for specifications and Figure 10 for a detailed view of the input
isolation transformer terminal block.
18. Punch a hole in the bottom of the MBM/PDM using a Greenlee punch or similar
device for wiring access.
Insert the supplied nylon bushing inside the wiring access hole.
19. Continue to the following chapter, “UPS-Mounted Bypass Switch Installation,” to
complete the installation.