102 Eaton 93PM UPS 480V Three-Wire 100 kW Frame Installation and Operation Manual 164000227—Rev 07
2. If dual feed, close the UPS Bypass input feeder circuit breaker.
3. Observe the UPS control panel becoming active, indicating logic power.
4. Verify no alarms are active.
5. Tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed.
6. Tap the MODULES CONTROLS tab on the secondary Control menu navigation bar. The UPM Select
screen is displayed.
7. On the UPM Select screen, select the UPM to start. The UPM Control Screen is displayed.
8. Tap the START MODULE button.
The UPM rectifier and inverter turn on. When the inverter reaches full voltage, the UPS is ready to transfer
to the Double Conversion mode and supply the critical load.
77..33..55 TTrraannssffeerr ffrroomm DDoouubbllee CCoonnvveerrssiioonn ttoo BByyppaassss MMooddee
To transfer the critical load to Bypass mode:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
1. Tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed.
2. Tap the GO TO BYPASS button.
The UPS transfers to Bypass mode. and the critical load is immediately supplied by the bypass source. If
the bypass source is not available, the power module remains on and an alarm sounds.
The BYPASS status indicator is illuminated. The power module remains on.
WARNING
Power is present inside the UPS cabinet.
77..33..66 TTrraannssffeerr ffrroomm BByyppaassss ttoo DDoouubbllee CCoonnvveerrssiioonn MMooddee
To transfer the critical load to Normal mode:
1. Tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed.
2. Tap the GO ONLINE button.
The UPS transfers to Double Conversion mode. If the power module is not available, the system remains
on bypass and an alarm sounds.
The NORMAL status indicator is illuminated.
77..33..77 TTrraannssffeerr ffrroomm EESSSS MMooddee ttoo DDoouubbllee CCoonnvveerrssiioonn MMooddee
To transfer the load to Standard Normal mode:
1. Tap the CONTROLS tab on the main menu navigation bar. The Control screen is displayed.
2. Tap the EAA CONTROLS tab on the secondary Control menu navigation bar. The EAA CONTROLS screen
is displayed.
3. Tap the DISABLE ESS button.
The UPS transfers to Double Conversion mode.
UPS Operating Instructions