6 Eaton 93PM UPS 480V Three-Wire 100 kW Frame Installation and Operation Manual 164000227—Rev 07
PredictPulse™ Remote Monitoring and Management Service PredictPulse is a subscription monitoring
and management service from Eaton that collects and analyzes data from connected power infrastructure
devices, providing us with the insight needed to make recommendations and take action on your behalf. It’s
also powered by CA Technologies, bringing together the best in hardware and software. Like a second set of
eyes on your power infrastructure, PredictPulse provides 24/7 remote monitoring of alarms and system
performance (load, temperature/humidity, battery health, energy savings and service level) to reduce downtime
risk and expedite repairs. PredictPulse also shares real-time status and trend information via an online
dashboard and smartphone mobile app (Apple and Android), giving subscribers insights about past and current
performance, a list of all active alarms, and asset management data (i.e., battery date codes, last and next
scheduled service dates, firmware versions). The service notifies customers of critical alarms, supports remote
diagnostics, and facilitates smart dispatch of technicians. PredictPulse requires a Power Xpert
®
Gateway
Minislot (PXGMS) connectivity card in an Minislot communication bay and an Environmental Monitoring Probe
(EMP) for battery temperature/humidity monitoring. See Chapter 9 Communication, for additional information
on monitoring and communication features.
11..22..1111 AAddddiittiioonnaall OOuuttppuutt SSuurrggee PPrrootteeccttiioonn
The Eaton 93PM UPS complies with ANSI 62.41 for line surges. However, if added security is required an
additional Surge Protection Device (SPD) can be installed. For this application, a 480V Delta Style SPD Type 1 or
Type 2 installed on the load side is recommended. The SPD must meet the Maximum Continuous Operating
Voltage (MCOV) for a 480V Delta Style SPD. Eaton offers a variety of SPD solutions including the Eaton SPD
Series with various kA ratings options.
11..33 BBaatttteerryy SSyysstteemm
Although not provided with the UPS, a battery system is required to provide emergency short-term backup
power to safeguard operation during brownouts, blackouts, and other power interruptions. The battery system
should be equipped with lead-acid batteries. An external battery disconnect switch or tie point must be used
when battery systems are located separate from the UPS cabinet and wiring exceeds the number of battery
terminals available.
A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided by the UPS, but is not
required for normal operation.
11..44 BBaassiicc SSyysstteemm CCoonnffiigguurraattiioonnss
The following basic UPS system configurations are possible:
Single UPS with one to four external battery cabinets
Single UPS with one to four external battery cabinets and accessory cabinets
Two to four UPSs with one to four external battery cabinets for each UPS
Two to four UPSs with one to four external battery cabinets for each UPS and accessory cabinets
The UPS system configuration can be enhanced by adding optional accessories such as a Remote Emergency
Power-off (REPO) control or Minislot communication cards.
11..55 UUssiinngg TThhiiss MMaannuuaall
This manual describes how to install and operate the Eaton 93PM UPS. Read and understand the procedures
described in this manual to ensure trouble-free installation and operation. In particular, be thoroughly familiar
with the REPO procedure or the LOAD OFF procedure, see Chapter 7 UPS Operating Instructions.
The information in this manual is divided into sections and chapters. The system, options, and accessories
being installed dictate which parts of this manual should be read. At a minimum, Chapter 1 Introduction through
Chapter 4 UPS System Installation and Chapter 7 UPS Operating Instructions should be examined.
Read through each procedure before beginning the procedure. Perform only those procedures that apply to the
UPS system being installed or operated.
Introduction

Table of Contents