UPS Installation Plan and Unpacking
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4 www.eaton.com/powerquality 3-11
Figure 3-8. Remote EPO Switch Dimensions
Weight and Center of Gravity with Left-Mounted Sidecar (letters A, B, and C map to Figure 3-7)
Internal
Battery Strings Frame
A
mm (in)
B
mm (in)
C
mm (in)
Installed Weight
kg (lb)
Eaton 93PM-50-1 UPS with UPS Top Entry Wiring Sidecar (no breakers)
0 Capacity 961 (37.8) 561 (22) 406 (16.0) 402 (887)
3 Capacity 849 (33.4) 549 (21.6) 445 (17.5) 821 (1812)
4 Capacity 864 (34) 547 (21.5) 449 (17.7) 926 (2043)
0 Redundant 954 (37.5) 562 (22.1) 409 (16.1) 418 (922)
Eaton 93PM-50-2 UPS with UPS Top Entry Wiring Sidecar (no breakers) 0 Redundant 1005 (39.5) 559 (22) 419 (16.5) 482 (1063)
Weight and Center of Gravity with Right-Mounted Sidecar (letters A, B, and C map to Figure 3-7)
Frame
A
mm (in)
B
mm (in)
C
mm (in)
Installed Weight
kg (lb)
Eaton 93PM-50-1 UPS with UPS Top Entry Wiring Sidecar (no breakers)
0 Capacity 961 (37.8) 561 (22) 346 (13.6) 402 (887)
3 Capacity 849 (33.4) 549 (21.6) 312 (12.3) 821 (1812)
4 Capacity 864 (34) 547 (21.5) 308 (12.1) 926 (2043)
0 Redundant 954 (37.5) 562 (22.1) 343 (13.5) 418 (922)
Eaton 93PM-50-2 UPS with UPS Top Entry Wiring Sidecar (no breakers) 0 Redundant 1005 (39.5) 559 (22) 335 (13.2) 482 (1063)
115.8
[4.56]
114.3
[4.50]
0.87
[0.22]
88.9
[3.50]
1.57
[0.40]
95.3
[3.57]
Front View
1/2" Knockout Pattern
(Typical 5 Sides