EasyManua.ls Logo

Eaton 9E - Table 3-5. UPS External Power Cable Terminations for the Eaton 9 E-40, 9 E-60;40, and 9 E-60;60

Eaton 9E
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS Installation Plan and Unpacking
3-8 Eaton 9E UPS (40–60 kVA, 208/220V) Installation and Operation Manual P-164000058—Rev 4 www.eaton.com/powerquality
The power wiring terminals are pressure terminations, UL and CSA rated at 90°C. See Table 3-5 for external
power cable terminations.
Figure 4-7 and Figure 4-8 show the location of the UPS power cable terminals.
Table 3-5. UPS External Power Cable Terminations for the Eaton 9E-40, 9E–60/40, and 9E–60/60
Terminal Function Terminal Function
Number and Size of Pressure
Termination
AWG or kcmil
Tightening Torque
Nm (lb in)
Screw Size and Type
AC Input to UPS Rectifier L1 Phase A 1 – #6-250 22.6 (200) 1/4 in. Hex
L2 Phase B 1 – #6-250 22.6 (200) 1/4 in. Hex
L3 Phase C 1 – #6-250 22.6 (200) 1/4 in. Hex
N Neutral 2 – #6-250 22.6 (200) 1/4 in. Hex
AC Input to Bypass L1 Phase A 1 – #6-250 22.6 (200) 1/4 in. Hex
L2 Phase B 1 – #6-250 22.6 (200) 1/4 in. Hex
L3 Phase C 1 – #6-250 22.6 (200) 1/4 in. Hex
N Neutral 2 – #6-250 22.6 (200) 1/4 in. Hex
AC Output to Critical Load L1 Phase A 1 – #6-250 22.6 (200) 1/4 in. Hex
L2 Phase B 1 – #6-250 22.6 (200) 1/4 in. Hex
L3 Phase C 1 – #6-250 22.6 (200) 1/4 in. Hex
N Neutral 2 – #6-250 22.6 (200) 1/4 in. Hex
DC Input from External Battery + Battery (+) 2 – #6-250 22.6 (200) 1/4 in. Hex
Battery (-) 2 – #6-250 22.6 (200) 1/4 in. Hex
Customer Ground Ground Ground 4 – #6-300 31.1 (275) 5/16 in. Hex
NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in Table 3-6.

Table of Contents

Related product manuals