32 Eaton 9PX Lithium-Ion User Guide DPD-9PX2206—Rev 01
Figure 16. BMS Auto Setup
Control
Go to bypass
Start battery test
Reset fault state
BMS auto setup
Reset battery life
Measurements
Control
Settings
Event log
Fault log
Identification
Register product
Menu
50% 100 %
Online mode
Press the
to advance the menu
2.7kW
3.0kVA
30min
1 EBM
Efficiency: 95%
BMS auto setup
Yes
No
Are you sure?
BMS auto setup
Done
4. Reset the battery life counter in the “Reset Battery Life” option of the control menu.
Figure 17. Battery Life Reset
Control
Go to bypass
Start battery test
Reset fault state
BMS auto setup
Reset battery life
Measurements
Control
Settings
Event log
Fault log
Identification
Register product
Menu
50% 100 %
Online mode
Press the
to advance the menu
2.7kW
3.0kVA
30min
1 EBM
Efficiency: 95%
Reset battery life
Yes
No
Are you sure?
Reset battery life
Done
Return the UPS to Normal Operation
If the UPS internal batteries and external battery packs were replaced without powering down the UPS:
1. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before
continuing. See section 8.1 Typical Alarms and Faults . If the
indicator is on, do not proceed until all
alarms are clear.
2. Verify that the
indicator illuminates solid, indicating that the UPS is operating normally and any loads
are powered and protected. The UPS should be in normal mode. 5.1 Start-up and Normal Operation .
If the UPS internal batteries and external battery packs were replaced and the UPS was powered off:
1. Verify that the internal batteries are connected. See Figure 15 .
2. If optional EBMs are installed, verify that the EBM are connected to the UPS.
Battery Settings Reset