38
4 Construction and Function
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
ATTENTION!
Only fuses approved by CEAG
Notlichtsysteme GmbH are permit-
ted to use.
SKU CG-S 2x3A
Fuses
On the front panel of the change-over module there are
per circuit
3 output fuses 5 AT / 250 V.
The nominal current should not exceed 3 A per circuit!
Fuse dimensions: 6.3 mm x 32 mm, sand filled.
Order no.: 400 71 689 047 / 10 qty./unit
Operation elements
Service-PIN
Beside the „Service“ lable there is a button which must be
operated when the system´s basic program is loaded. The
basic programming occurs factory made.
1
)
Indicators
ON LED
The LED lights up when the voltage is present at the output
terminals.
Fault LED
The LED lights up, when one or more luminaires are faulty.
Additional Features
Mixed operation of
maintained light, non-maintained light and switched
maintained light in one circuit by using of CEAG EVGs/modules
with CG-S marking can be programmed without any additional
data cable.
Individual monitoring of
up to 20 luminaires per circuit
Individual switchin each circuit
Separate fusing for mains and battery operation
Among unipolar earth connection
in AC operation fault free DC operation can continue
Easy access to fuses
Separate savings for mains and battery operation
Connected rating per circuit660 W
Inrush current per circuit 250 A/ms
Typical change-over time AC on DC = 450 ms
Components for circuit change-over module
SKU 2 x 3 A CG-S
(2 circuits each 3 A rated current)
The current module is connected to the controller via the BUS.
At the device configuration an address is allocated via the
controller. This occures factory made.
All functions as switching mode, monitoring function can be
programmed via the controller.
Will the circuit change over module be refitted or replaced
the programming must be changed.