7.0
GENERAL
Figure 54 is a close-up view of a breaker with one insulat-
ing barrier removed to show the arc chute in place on the
pole unit. Similar designs of arc chutes are used on the
DS416, DS420 and DS632 assemblies with a smaller
one on the DS206 and a slightly larger one on the
DS840.
SEC
ONO
ARY
CONTACT
COVER
Fig. 54 Breaker with Barrier Removed to Show Mounting
of
Arc
Chutes (391072)
Fig.
55
DS-206
Arc
Chute with Details (383973)
ll'lSULATING
INSULATING
lll'ACER PLATE
TOP
STRIPS STEEL PLATES
Fig.
56
DS-4161420
Arc
Chute with Details (391270)
INSULATING
INSULATING
SPACER
PLATE
TOP
STRIPS
STEEL PLATES
Fig.
57
DS-632
Arc
Chute with Details (391269)
The arc chute fits well down over the arcing contacts so
that the arc is confined inside the chute at all times and
for all values of current.
In
the arc chute, immediately
above the arcing contacts, are spaced crosswise vertical
steel splitter plates having an inverted "V" notch to attract
Effective