46 INSTALLATION AND OPERATION MANUAL 25-16328-B November 2020 www.eaton.com
Section 3: Panel controls & indicators
Specifications
Loop load Min Nom Max Units
Quiescent current 310 μA
Operating voltage 18 30 V DC
Inputs
Trigger resistance 5.6
End of line resistor 22
Short circuit fault threshold resistance 1
Open circuit fault threshold resistance 33
Environmental
Operating temperature -10 +60 °C
Humidity (non condensing) 95 %RH
Standards
EN54 : Pt2 & 4
BS5839 : Pt1 (installation)
Compatibility
Suitable for use with Eaton analogue addressable fire systems
Physical
Dimensions 63mm x 35mm x 18.5mm
Weight > 0.1gm
Ingress protection IP40
Short circuit isolator
This addressable device contains an integral short circuit isolator, which operates
between the – IN terminal and the – OUT terminal. The isolator operates in
conjunction with Eaton Analogue Addressable Control Panels when a low parallel
resistance fault of typically 200? is present between the +VE and –VE of the
loop wiring.
Short circuit isolation data (integral with each device)
Total loop resistance for correct operation of
short circuit isolator
50
Ω
(max)
Continuous current allowable through isolator 700mA (max)
Isolator resistance in closed state 0.13
Ω
(max)
Leakage current into direct short circuit with isolator open 13mA (max)
Parallel fault resistance to be seen at the control panel
for isolators to open
200
Ω
(typ)