EDR-5000 IM02602007E
Parameter Set Parameters of the Reactive Power Protection Module
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
Blo TripCmd Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
ExBlo TripCmd Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
LOP Blo Measuring Circuit Supervision Voltage Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
CTS Blo Measuring Circuit Supervision Current Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
www.eaton.com 704