EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
Pickup Q> Over(load) Reactive Power Pickup Value. Monitoring the
maximum allowed reactive power of the electrical
equipment like transformers or overhead lines). If the
maximum value is exceeded, a condensator bank could
be switched off. Definition for VAn is as follows: VAn =
SQRT(3) * VT secondary rating * CT secondary rating
(I=1/5A) for wye or VAn = 3 * VT secondary
rating/SQRT(3) * CT secondary rating (I=1/5A) for delta
connections.
Only available if: Device Planning: PQS.Mode = Pickup
Q>
0.003 - 10.000VAn 1.20VAn [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
Pickup Q< Under(load) Reactive Power Pickup Value. Monitoring
the minimum value of the reactive power. If it falls below
the set value, a condensator bank could be switched on.
Definition for VAn is as follows: VAn = SQRT(3) * VT
secondary rating * CT secondary rating (I=1/5A) for wye
or VAn = 3 * VT secondary rating/SQRT(3) * CT
secondary rating (I=1/5A) for delta connections.
Only available if: Device Planning: PQS.Mode = Pickup
Q<
0.003 - 10.000VAn 0.80VAn [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
Pickup Qr> Overload Reverse Reactive Power Pickup Value
Definition for VAn is as follows: VAn = SQRT(3) * VT
secondary rating * CT secondary rating (I=1/5A) for wye
or VAn = 3 * VT secondary rating/SQRT(3) * CT
secondary rating (I=1/5A) for delta connections.
Only available if: Device Planning: PQS.Mode = Pickup
Qr>
0.003 - 10.000VAn 0.020VAn [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
Pickup Qr< Under Reverse Definition for VAn is as follows: VAn =
SQRT(3) * VT secondary rating * CT secondary rating
(I=1/5A) for wye or VAn = 3 * VT secondary
rating/SQRT(3) * CT secondary rating (I=1/5A) for delta
connections.
Only available if: Device Planning: PQS.Mode = Pickup
Qr<
0.003 - 10.000VAn 0.80VAn [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
t Tripping delay 0.00 - 1100.00s 0.01s [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
www.eaton.com 705