EDR-5000 IM02602007E
Set Parameters of the Power Factor Module
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Blo TripCmd Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
ExBlo TripCmd Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Trig Mode Trigger Mode. Should the Module be triggered if the
Current Phasor is leading to the Voltage Phasor = Lead?
Or should the Module be triggered if the Current Phasor
is lagging to the Voltage Phasor = Lag?
leading,
lagging
lagging [Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Trigger-PF This is the power factor where the relay will pick up 0.5 - 0.99 0.7 [Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Res Mode Trigger Mode. Should the Module be triggered if the
Current Phasor is leading to the Voltage Phasor = Lead?
Or should the Module be triggered if the Current Phasor
is lagging to the Voltage Phasor = Lag?
leading,
lagging
lagging [Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
www.eaton.com 717