EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
Reset-PF This setting is the power factor, at which the relay will
reset the power factor trip. It is like setting a hysteresis
for the Trigger setting.
0.5 - 0.99 0.9 [Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
t-trip Tripping delay 0.00 - 300.00s 0.00s [Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
t-Pickup Comp Pre-trigger time for the Compensation Signal. When this
timer is elapsed the compensation signal will be
activated.
0.00 - 300.00s 5.00s [Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
t-Reset Comp Reset (Post-trigger) time of the Compensation Signal.
When this timer is elapsed the compensation signal will
be deactivated.
0.00 - 300.00s 5.00s [Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
States of the Inputs of the Power Factor Module
Name Description Assignment via
ExBlo1-I Module Input State: External Blocking [Protection Para
/Global Prot Para
/Power Factor-Prot
/PF-55D[1]]
ExBlo2-I Module Input State: External Blocking [Protection Para
/Global Prot Para
/Power Factor-Prot
/PF-55D[1]]
ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command [Protection Para
/Global Prot Para
/Power Factor-Prot
/PF-55D[1]]
www.eaton.com 718