EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
Phi-Power Trigger Phi-Power (Positive Phase Sequence System)
Only available if: QV-Method = Power Angle Supervision
0 - 10° 3° [Protection Para
/<1..4>
/Q->&V<
/Decoupling]
Q min QV Trigger for the Reactive Power (Positive Phase
Sequence System)
Only available if: QV-Method = Pure Reactive Power
Superv
0.01 - 0.20VAn 0.05VAn [Protection Para
/<1..4>
/Q->&V<
/Decoupling]
t1-QV First timer. If this timer has elapsed, a trip signal will be
issued to the (local) energy resource.
0.00 - 2.00s 0.5s [Protection Para
/<1..4>
/Q->&V<
/Decoupling]
t2-QV Second timer. If this timer is elapsed, the an trip signal
will be issued to the PCC (Point of Common Coupling)
0.00 - 4.00s 1.5s [Protection Para
/<1..4>
/Q->&V<
/Decoupling]
Reclosure Release
Cond
This singal indicates that the mains voltage is recovered. V Internal Release,
V Ext Release PCC
V Internal
Release
[Protection Para
/<1..4>
/Q->&V<
/Reclosure
/Release]
PCC Fuse Fail VT
Fk
Blocking if the fuse of a voltage transformer has tripped
at the PCC.
Only available if: Reclosure Release Cond = V Ext
Release PCC
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Q->&V<
/Reclosure
/Release]
Decoupling1 Decoupling signal that triggers the reclosure. ReclosureTrigger -.- [Protection Para
/<1..4>
/Q->&V<
/Reclosure
/ReclosureTrigger]
Decoupling2 Decoupling signal that triggers the reclosure. ReclosureTrigger -.- [Protection Para
/<1..4>
/Q->&V<
/Reclosure
/ReclosureTrigger]
www.eaton.com 739