Parameter Description Setting range Default Menu path
Decoupling3 Decoupling signal that triggers the reclosure. ReclosureTrigger -.- [Protection Para
/<1..4>
/Q->&V<
/Reclosure
/ReclosureTrigger]
Decoupling4 Decoupling signal that triggers the reclosure. ReclosureTrigger -.- [Protection Para
/<1..4>
/Q->&V<
/Reclosure
/ReclosureTrigger]
Decoupling5 Decoupling signal that triggers the reclosure. ReclosureTrigger -.- [Protection Para
/<1..4>
/Q->&V<
/Reclosure
/ReclosureTrigger]
Decoupling6 Decoupling signal that triggers the reclosure. ReclosureTrigger -.- [Protection Para
/<1..4>
/Q->&V<
/Reclosure
/ReclosureTrigger]
VLL> Release Minimum voltage (line-to-line) for reclosure (Restoration
Voltage)
Only available if: Reclosure Release Cond = V Internal
Release
0.70 - 1.00Vn 0.95Vn [Protection Para
/<1..4>
/Q->&V<
/Reclosure
/Release]
f< Lower frequency limit for the reclosure (Restoration
Voltage)
40.00 - 69.90Hz 47.5Hz [Protection Para
/<1..4>
/Q->&V<
/Reclosure
/Release]
f> Upper freqeuncy limit for the reclosure 40.00 - 69.90Hz 50.05Hz [Protection Para
/<1..4>
/Q->&V<
/Reclosure
/Release]