Page #146 background image
EFX48-xx Series with RM3-340/440 Installation and Operation Guide
146
Copyright © 2019 Eaton Corporation. All Rights Reserved.
IPN March 2019
No AC delay
systemMainsFailDwell
AC fail delay
(s)
60 10 900 10
Over-
current
restart
systemOvercurrentRestartEnable
Restart enable yes no yes n/a
Interval
systemOvercurrentRestartDelay
Interval (s) 360 60 900 5
Attempts
systemOvercurrentRestartLimit
Retry limit 5 1 9 1
System
nominal
bus
voltage
Float
systemBusVoltageNominal
Float (V) 54.5 39.0 60.0 0.1
* Factory defaults may not be correct for your installation. You need to set-up your own configuration file to
over-write the factory defaults after a factory reset if necessary.

Table of Contents