3 Commissioning
3.1 Setting the rated operational current
48 Elektronischer Motorstarter EMS/Electronic Motor Starter EMS 04/15 MN03407009Z-DE/EN www.eaton.com
3 Commissioning
After the supply voltage is applied, all four LEDs will light up once to ensure
that they are working and will then start indicating the device‘s operating sta-
tus. After this LED test, the electronic motor starter will be ready for you to
set the rated operational current. To be able to set the rated operational cur-
rent, the device must not be indicating any faults (The ERR LED must be off).
3.1 Setting the rated operational current
Use the 240° potentiometer to set the motor‘s rated operational current.
There are 16 rated operational current settings available.
While holding down the Reset pushbutton the status LEDs will show the
current that has been set, in binary.
In safety-oriented ATEX applications, make sure to double-check that
you have set the correct rated operational current by having the LEDs
show it.