EasyManua.ls Logo

Eaton Magnum DS Series - Page 22

Eaton Magnum DS Series
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com22
Magnum DS - Product specific information
Table 6. Magnum DS switchgear class UL 1066 low voltage power circuit breakers ANSI continued
Frame
amperes
Breaker
type
catalog
position
1–6
Frame
type
rms Symmetrical current ratings kA 50/60 Hz
Available
current
sensor
and rating
plugs for
digitrip rms
trip unit
(establishes
breaker I
n
rating)
Poles
available
Interruption
rating at
254 Vac
Interruption
rating at
508 Vac
Interruption
rating at
635 Vac
Short
time
withstand
rating
@254/
508Vac
Short
time
withstand
rating
@635Vac
Fixed
internal
inst
trip
2000 MDN-620 Narrow 65 65 65 65 65 n/a 200, 250, 300,
400, 600, 800,
1000, 1200,
1600, 2000
3 & 4
MDN-C20 Narrow 100 100 65 35 35 18xIn 3 & 4
MDS-620 Standard 65 65 65 65 65 n/a 3 & 4
MDS-820 Standard 85 85 85 85 85 n/a 3 & 4
MDS-C20 Standard 100 100 100 85 85 85 3 & 4
MDS-H20 Standard 130 130 130 85 85 85 3
MDS-L20 Standard 200 200 200 n/a 3
MDS-X20 Standard 200 200 65 30 30 30 3
2500 MDS-625 Standard 65 65 65 65 65 n/a 200, 250, 300,
400, 600, 800,
1000, 1200,
1600, 2000,
2500
3 & 4
MDS-825 Standard 85 85 85 85 85 n/a 3 & 4
MDS-C25 Standard 100 100 100 100 85 85 3 & 4
MDS-H25 Standard 130 130 130 85 85 85 3
3200 MDS-632 Standard 65 65 65 65 65 n/a 200, 250, 300,
400, 600, 800,
1000, 1200,
1600, 2000,
2500, 3200
3 & 4
MDS-832 Standard 85 85 85 85 85 n/a 3 & 4
MDS-C32 Standard 100 100 100 85 85 85 3 & 4
MDS-H32 Standard 130 130 130 85 85 85 3
MDS-X32 Double 200 200 50 50 50 3
4000 MDS-840 Double 85 85 85 85 85 n/a 2000, 2500,
3200, 4000
3 & 4
MDS-C40 Double 100 100 100 100 100 n/a 3 & 4
MDS-H40 Double 130 130 130 130 130 n/a 3
MDS-X40 Double 200 200 50 50 50 3
MDN-640 Double
Narrow
65 65 65 65 65 n/a 3 & 4
MDN-840 Double
Narrow
85 85 65 85 65 n/a 3 & 4
MDN-C40 Double
Narrow
100 100 65 100 65 n/a 3 & 4
MDD-X40 Double 200 200 100 100 100 n/a 3
5000 MDS-850 Double 85 85 85 85 85 n/a 2500, 3200,
4000, 5000
3 & 4
MDD-X50 Double 200 200 100 100 100 n/a 3
MDS-C50 Double 100 100 100 100 100 n/a 3 & 4
MDS-H50 Double 130 130 130 130 130 n/a 3
MDS-X50 Double 200 200 50 50 50 3
Interrupting ratings shown based on breaker equipped with integral digitrip rms trip unit. Interruption ratings for non-automatic breakers are equal to
the published withstand rating.
Magnum MDSL current limiting power circuit breaker with integral current limiters. Current limiter selected determines short time and fixed instanta-
neous trip rating.
Magnum MDSX current limiting power circuit breaker with fast opening contacts.
Product to be tested. Contact Eaton for product rating.
Breaker applied in a tested fan cooled enclosure.
Not released.
1
2
3
3
3
3 5
4
4
4
2 2
1
2
3
4
5
6
Courtesy of NationalSwitchgear.com