9
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 59
Technical data and endurance information for installation
Technical data for usual service conditions (0°C to 40°C)
Ambient temperatures & thermal derating tables
Magnum breakers are tested and fully rated for use in
ambient temperatures from 0°C to 40°C. Thermal de-rating
tables are provided for different Magnum breakers operating in
switchboards at various ambient temperatures above 40°C.
The switchboard’s ambient should be estimated using an
industry accepted calculation method.
Magnum DS and SB ANSI temperature derating tables
Table 19. Calculated de-rated capacity ANSI standard
Frame Actual ambient temperature (°C)
40 45 50 55 60 70
800 800 800 800 794 738 612
1600 1600 1600 1600 1600 1592 1321
2000 2000 2000 1995 1869 1735 1439
2500 2500 2395 2259 2116 1965 1630
3000 3000 2845 2684 2514 2334 1936
3200 3200 3098 2922 2737 2541 2108
4000 4000 4000 3815 3574 3318 2752
5000 5000 5000 4716 4417 4101 3402
Table 20. Calculated de-rated capacity ANSI narrow
Frame Actual ambient temperature (°C)
40 45 50 55 60 70
800 800 800 800 800 800 800
1200 1200 1200 1200 1200 1200 1101
1600 1600 1600 1526 1429 1327 1101
2000 2000 1916 1807 1693 1572 1304
Table 21. Calculated de-rated capacity ANSI
MDSL Magnum
Frame Actual ambient temperature (°C)
40 45 50 55 60 70
800 800 800 800 800 800 763
1600 1600 1600 1600 1521 1413 1172
2000 2000 2000 1976 1851 1718 1425
Shaded means no loss in derating
Magnum IEC temperature derating tables
Table 22. Calculated de-rated capacity for
IEC standard Magnum
Frame Actual ambient temperature (°C)
40 45 50 55 60 70
800 800 800 800 800 800 800
1000 1000 1000 1000 1000 1000 1000
1250 1250 1250 1250 1250 1250 1250
1600 1600 1600 1600 1600 1600 1600
2000 2000 2000 2000 2000 2000 2000
2500 2500 2500 2500 2500 2500 2482
3200 3200 3109 2992 2871 2746 2482
4000SW 4000 4000 4000 4000 4000 3615
4000DW 4000 4000 4000 4000 4000 4000
5000 5000 5000 5000 5000 5000 5000
6300 6300 6300 6260 6008 5747 5193
Table 23. Calculated de-rated capacity for
IEC narrow Magnum
Frame Actual ambient temperature (°C)
40 45 50 55 60 70
800 800 800 800 800 800 800
1000 1000 1000 1000 1000 1000 1000
1250 1250 1250 1250 1250 1100 1000
1600 1600 1600 1600 1600 1500 1350
2000 2000 2000 2000 2000 1800 1650
4000 NDW 4000 4000 4000 4000 3928 3549
Shaded means no loss in derating
Courtesy of NationalSwitchgear.com