MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com38
Magnum IEC - Product specific information
Table 9. Magnum IEC 60947-2 rated air circuit breakers continued
Frame
amperes
Breaker
type
Frame
type
rms symmetrical current ratings kA
Available
current
sensor
and
rating
plugs for
digitrip
rms trip
unit
(estab-
lishes
breaker
I
n
rating)
KEMA/
KEUR CCC
Poles
avail-
able
Inter-
rupting
@ 240
Vac
Icu = Ics
Inter-
rupting
@ 440
Vac
Icu = Ics
Inter-
rupting
@ 690
Vac
Icu = Ics
With-
stand
rating
Icw
1-Sec @
440V/
690V
With-
stand
rating
Icw
3-Sec
Fixed
internal
inst
trip
2500 MWI-625 Standard 65 65 65 65 n/a 200, 250,
300, 400,
630, 800,
1000, 1250,
1600, 2000,
2500
X X 3 & 4
MWI-825 Standard 85 85 85 85 65 X X 3 & 4
MWI-C25 Standard 100 100 85 85 65 85 3 & 4
MWI-H25 Standard 125 125 125 85 65 X X 3 & 4
3200 MWK-232 Standard 85 85 85 85 65 3200 3 & 4
MWI-632 Standard 65 65 65 65 50 200, 250,
300, 400,
630
X X 3 & 4
MWI-832 Standard 85 85 85 85 65 X X 3 & 4
MWI-C32 Standard 100 100 85 85 65 85 X X 3 & 4
MWI-H32 Standard 125 3 & 4
4000 MWI-64N Double 65 65 65 65 n/a 2000,
2500,
3200,
4000
X X 3 & 4
MWN-64N Double
Narrow
66 66 66 66 n/a X X 3 & 4
MWI-641 Standard 66 66 66 66 n/a X X 3 & 4
MWI-84N Double 85 85 85 85 n/a X X 3 & 4
MWN-84N Double
Narrow
85 85 66 85/66 66 X X 3 & 4
MWI-841 Standard 85 85 85 85 66 X X 3 & 4
MWI-C4N Double 100 100 100 100 n/a X X 3 & 4
MWN-C4N Double
Narrow
105 105 66 105/66 66 X X 3 & 4
MWI-C41 Standard 105 105 85 85 n/a X X 3 & 4
5000 MWI-85N Double 85 85 85 85 n/a 2500,
3200,
4000, 5000
X X 3 & 4
MWI-C5N Double 100 100 100 100 n/a X X 3 & 4
6300 MWI-86N Double 85 85 85 85 n/a 3200,
4000,
5000, 6300
X X 3 & 4
MWI-C6N Double 100 100 100 100 n/a X X 3 & 4
Interrupting ratings shown based on breaker equipped with integral digitrip rms trip unit. Interruption ratings for non-automatic breakers
are equal to the published withstand rating.
690V rating is not certified Kema/KEUR.
1100V Icu rating is 25kA.