MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 45
Magnum trip units and communication devices
Digitrip 1150+
The Digitrip 1150+ trip unit
offers advanced protection
and power monitoring
including harmonics,
breaker health, waveform
capture, and advanced
communications options.
It eliminates the need for
separate metering packages
which saves cost, space and
installation effort. Extensive
operational information is
available across the INCOM
communications for increased
remote monitoring and control
capability. The Digitrip 1150+
includes the Eaton's Arc-
ash Reduction Maintenance
System (ARMS). For a
complete discussion of Digitrip
1150+ Trip Unit capabilities,
refer to its instruction leaet
IL70C1036.
The following is a summary of
the 1150+ product features:
LSI, LSIG and LSIA
Protection
Arc-flash Reduction
Maintenance System
(ARMS) functionality- On/Off
Pickup Levels
24 Character, 3-line Digital
LED Display
Unit Status LED (Green)
Indicator
Programmable Protective
Settings:
I2t and I4t Curves
Adjustable Long Time and
Short Time Pick-up / Delay
Moderately Inverse, Very
Inverse and Extremely
Inverse IEEE Curves
IEC Curves
Neutral Protection (Model
LSIG and LSIA Trip Unit)
Adjustable Instantaneous
Pick-up with
Instantaneous Off Setting
Adjustable Ground Fault
Pick-up / Delay (Trip or
Alarm)
Undervoltage and
Overvoltage Protection
(Trip or Alarm)
Underfrequency and
Overfrequency Protection
(Trip or Alarm)
Reverse Power (Trip)
Voltage Unbalance
Protection (Trip or Alarm)
Phase Rotation (Alarm)
Long Time (Thermal)
Memory Trip
Overtemperature Trip when
the temperature exceeds
85°C
Power and Energy Metering
Display:
Current (±1% 3-phase,
neutral and ground)
Voltage L-L (±1%)
Frequency (±0.05 Hz)
Power & Energy (±2%)
Kilowatts (kW)
Kilowatt Hours (kWH)
Kilovoltamperes (kVAR)
Power Factor
kVA Hours
Fixed 15 Minute Demand
for kW, kVAR & kVA
Sliding 15 Minute
Demand for kW or kVA
Power Quality and Breaker
Health Metering and
Monitoring:
Waveform Capture
% Total Harmonic
Distortion
Programmable Alarm
Contacts
Breaker Control (Remote
Open & Close via
Communications)
Operations Counter
Test Port with Cover to
receive Digitrip Hand Held
Tester
Power Receptacle for
Auxiliary Power Module to
power up Trip Unit when
Breaker in Disconnect or
Remove position
Integral Self-Test
Accessory Bus for
Additional Programmable
Contacts
Battery Included to Power
LEDs
Reset/Battery Test
Pushbutton
Communications
Functions and Data
ote:N The Digitrip 1150+
family of trip units incorporates
two microprocessors in their
design. One processor is devoted
fully to the task of current
protection functions. The second
microprocessor provides the
voltage protection, display,
communications, metering,
harmonic calculations, alarming,
and auxiliary relay functions.
These advanced features and the
communications capability require
that auxiliary power be provided by
the customer to the circuit breaker
Power Relay Module.
Click here or search for
70C1036’ on www.eaton.
com, for more detailed
information on Magnum
Digitrip 1150 trip units
Digitrip 1150+
Courtesy of NationalSwitchgear.com