EasyManua.ls Logo

Eaton Magnum DS Series - Page 49

Eaton Magnum DS Series
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 49
Magnum trip units and communication devices
0 0 2
1
2
3
4
(Y)
(BL)
0 0 1
Typical IBM
compatible
computer
Breaker interface
Monitor (BIM II)
See view A
Twisted Pair.
No. 18 AWG
Baud rate
1200 or 9600
Cutoff shield or connect to
unused customer terminal—
Do not ground
3-Digit
INCOM address
Eaton CONI card
Typical Magnum
circuit breaker with
Digitrip trip unit
View A
Res.
2 4
3
3
1
1
4
INCOM network
Notice: 100 ohm 1/2W
terminating resistor required
on network even if network is
unused
1. Refer to master circuit breaker connection diagrams
in Appendix C.
2. Modular telephone connector, Type RJ11, supplied
by user.
3. Ground shielding at computer BIM II as shown.
Where devices are daisy-chained, interconnect shielding,
but do not ground the connection.
4. 100 ohm ½ watt carbon resistor required at last
breaker. See T.D. 17-513. Also insert 100 ohm resistor to
terminator at CONI card (via switch on CONI).
5. See page 55 for programming INCOM function.
6. AEM II is compatible with Digitrip 1150 with AEM II
rmware Version 7.1 and the Digitrip 1150 set in the DT
910 COMM mode (see page 55).
7. Breaker Interface Module (BIM II) Version 3.12 is
compatible with Digitrip 1150
Cat. No. 11 ****. BIM II Version 3.20 or greater is
compatible with Digitrip 1150
Cat. No. 11 **** and Cat. No. 11P ****.
Courtesy of NationalSwitchgear.com

Table of Contents

Other manuals for Eaton Magnum DS Series

Related product manuals