Engineering
04/10 MN04020001Z-EN
26
Safety and switching
Fuses and cable cross-sections
The fuses and wire cross-sections allocated for power-side 
connections depend on the rated mains current I
LN
 of the 
frequency inverter (without mains reactor).
The recommended fuses and their assignment to the frequency 
inverters are listed in page 157 the appendix.
The national and regional standards (for example VDE 0113, EN 
60204) must be observed and the necessary approvals (for 
example UL) at the site of installation must be fulfilled.
When the device is operated in a UL-approved system, use only 
UL-approved fuses, fuse bases and cables.
The leakage currents to ground (to EN 50178) are greater than 
3.5 mA. The connection terminals marked PE and the housing 
must be connected with the ground circuit.
The leakage currents for the individual performance variables are 
listed in the appendix on page 147 ff.
Cables and fuses
The cross-sections of the cables and line protection fuses used 
must correspond with local standards.
For an installation in accordance with UL guidelines, the fuses and 
copper cable that are UL-approved and have a heat-resistance of 
+60/75 °C are to be used.
Use power cables with insulation according to the specified mains 
voltages for the permanent installation. A shielded cable is not 
required on the mains side.
A completely (360°) shielded low impedance cable on the motor 
side is required. The length of the motor cable depends on the 
RFI class and must not exceed 30 m for the M-Max
TM
.
Residual-current device (RCD)
RCD (Residual Current Device): Residual current device, residual 
current circuit breaker (FI circuit breaker)
Residual current circuit breakers protect persons and animals from 
the existence (not the origination) of impermissibly high contact 
voltages. The prevent dangerous, in cases deadly injuries caused 
by electrical accidents and also serve as fire prevention.
Frequency inverters work internally with rectified AC currents. If an 
error occurs, the DC currents can block an RCD circuit breaker of 
type A from triggering and therefore disable the protective 
functionality.
Safety-relevant leakage currents can occur while handling and 
when operating the frequency inverter, if the frequency inverter is 
not grounded (because of a fault).
Leakage currents to ground are mainly caused by foreign 
capacities with frequency inverters; between the motor phases 
and the shielding of the motor cable and via the Y-capacitors of 
the noise filter. The size of the leakage current is mainly dependent 
upon the:
• length of the motor cable,
• shielding of the motor cable,
• height of the pulse frequency (switching frequency of the 
inverter),
• design of the noise filter,
• Grounding measures at the site of the motor.
h
Caution!
When selecting the cable cross-section, take the voltage 
drop under load conditions into account. 
The consideration of other standards (e.g. VDE 0113 or 
VDE 0289) is the responsibility of the user.
h
Caution! 
The specified minimum PE conductor cross-sections (EN 
50178, VDE 0160) must be maintained.
h
Choose the cross-section of the PE conductor in the motor 
lines at least as large as the cross-section of the phase 
lines (U, V, W).
j
Warning!
With frequency inverters, only AC/DC sensitive residual 
current circuit breakers (RCD type B) are to be used 
(EN 50178, IEC 755).
Identification on the residual-current circuit-breakers
AC/DC sensitive 
(RCD, type B)
h
Caution! 
Debounced inputs may not be used in the safety 
circuit diagram.
Residual current circuit breakers (RCD) are only to be 
installed between the AC power supply network and the 
frequency inverter.
h
The leakage current to ground is greater than 3.5 mA with 
a frequency inverter. Based on the requirements of 
EN 50178, an increased ground (PE) has to be connected. 
The cable cross-section must be at least 10 mm
2
 or 
consist of two separately connected ground cables.
h
As long as you use residual current circuit breakers, they 
must be suitable for:
• the protection of installations with DC current 
component in case of fault scenario (RCD type B),
• high leakage currents (300 mA),
• brief discharges of pulse current spikes.