www.eaton.com Page 4-13
MP-4000 IB02602002E
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
(DEFAULT SELECTION AND
VALUE AS SHIPPED IN BOLD)
VALUE SELECTED
8 Choose:
MB A ON
MB T ON
or
MB OFF
ENABLE MOTOR BEARING ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between MB A ON, MB T ON, and
MB OFF
9 Choose:
LB A ON
LB T ON
or
LB OFF
ENABLE LOAD BEARING ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between LB A ON, LB T ON, and
LB OFF
10 Choose:
AX A ON
AX T ON
or
AX OFF
ENABLE AUXILIARY RTD TEMP ALARM
OR TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between AX A ON, AX T ON, and
AX OFF
11 Choose:
SX A ON
SX T ON
or
SX OFF
ENABLE STARTS PER TIME TRIP OR
ALARM TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between SX A ON, SX T ON, and
SX OFF
12 Choose:
TBS T ON
or
TBS OFF
ENABLE TIME BETWEEN STARTS TRIP
TO ACTIVATE AUX2 RELAY OUTPUT
OR DISABLE
Toggles between TBS T ON and TBS OFF
13 RTDF ON
or
RTDF OFF
ENABLE INDIVIDUAL RTD CHANNEL
FAILURE TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between RTDF ON and RTDF OFF
14 RCOM ON
or
RCOM OFF
ENABLE RTD MODULE
COMMUNICATION
FAILURE TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between RCOM ON and RCOM OFF
15 IOC A ON
IOC T ON
or
IOC OFF
ENABLE INSTANTANEOUS TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between IOCT ON and IOCT OFF
16 PH R ON
or
PH R OFF
ENABLE PHASE REVERSAL TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between PH R ON and PH R OFF
17 INSQ ON
or
INSQ OFF
ENABLE INCOMPLETE SEQUENCE
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between INSQ ON and INSQ OFF
18 REMT ON
or
REMT OFF
ENABLE REMOTE TRIP TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
Toggles between REMT ON and REMT OFF
19 DIFT ON
or
DIFT OFF
ENABLE DIFFERENTIAL TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between DIFT ON and DIFT OFF
20 INCT ON
or
INCT OFF
ENABLE INCOM TRIP TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
Toggles between INCT ON and INCT OFF
21 TRNT ON
or
TRNT OFF
ENABLE TRANSITION TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between TRNT ON and TRNT OFF
22 ZSWT ON
or
ZSWT OFF
ENABLE ZERO SPEED SWITCH TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between ZSWT ON and ZSWT OFF
23 TBYP ON
or
TBYP OFF
ENABLE TRIP BYPASS TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
Toggles between TBYP ON and TBYP OFF
PAGE 11, SP A OUT SETTING FOR ANALOG OUTPUT CONFIGURATION
1 MAX 100 4-20 mA OUTPUT
Select one of MAX 100, MAX 125, MAX
WRTD or MAX %I2T
MAX 125 MAX 100-20 mA FOR 100% FLA
MAX WRTD MAX 125-20 mA FOR 125% FLA
MAX %I2T MAX WRTD - 20 mA FOR TRIP LEVEL
MAX %I2T - 20 mA FOR 100% I2T