Page 4-14
www.eaton.com
IB02602002E MP-4000
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
(DEFAULT SELECTION AND
VALUE AS SHIPPED IN BOLD)
VALUE SELECTED
PAGE 12, SP SYS SETTINGS FOR SYSTEM CONFIGURATION
1 TP MODE X CONFIGURE TRIP RELAY OUTPUT TO
BE MODE 1 --
TRIP RELAY ENERGIZES ON TRIP
EVENT OR MODE 2 --TRIP RELAY
ENERGIZES ON POWER UP AND
DE-ENERGIZES ON TRIP EVENT
Toggles between TP MODE 1 and TP MODE2
2 AL MODE X CONFIGURE ALARM RELAY OUTPUT
TO BE MODE 1 - ALARM RELAY
ENERGIZES ON ALARM EVENT OR
MODE 2 - ALARM RELAY ENERGIZES
ON POWER UP AND DE-ENERGIZES
ON ALARM EVENT
Toggles between AL MODE1 and AL MODE2
3 AX1 MOD X CONFIGURE AUX1 RELAY OUTPUT TO
BE MODE 1 - AUX1 RELAY ENERGIZES
ON AUX1 EVENT OR MODE 2 - AUX1
RELAY ENERGIZES ON POWER UP
AND DE-ENERGIZES ON AUX1 EVENT
Toggles between AX1 MOD1 and AX1 MOD2
4 AX2 MOD X CONFIGURE AUX2 RELAY OUTPUT TO
BE MODE 1 - AUX2 RELAY ENERGIZES
ON AUX2 EVENT OR MODE 2 - AUX2
RELAY ENERGIZES ON POWER UP
AND DE-ENERGIZES ON AUX2 EVENT
Toggles between AX2 MOD1 and AX2 MOD2
5 MAN I2T
or
AUTO I2T
AUTO OR MANUAL I2T RESET
Toggles between MAN I2T and AUTO I2T
6 RUN PGM
or
STOP PGM
ENABLE UNIT TO BE PROGRAMMED
WHILE MOTOR IS RUNNING
Toggles between RUN PGM and STOP PGM
7 EMRG EN
or
EMRG DIS
EMERGENCY OVERRIDE ENABLE
EMRG EN - ENABLE EMERGENCY
OVERRIDE
EMRG DIS - DISABLE EMERGENCY
OVERRIDE
Toggles between EMRG EN and EMRG DIS
8 12 HOUR
or
24 HOUR
SET MONITOR MODE CLOCK DISPLAY
12 HOUR - AM/PM TIME DISPLAYED
24 HOUR - 24 HOUR TIME DISPLAYED
Toggles between 12 HOUR and 24 HOUR
9 MONTH XX SET REAL TIME CLOCK MONTH
Month 1-12 (1 month increments) (none)
10 DAY XX SET REAL TIME CLOCK DAY
Day 1-31 (1 day increments) (none)
11 YEAR XX SET REAL TIME CLOCK YEAR
Year 0-99 (1 year increments) (none)
12 HOUR XX SET REAL TIME CLOCK HOUR
Hour 0-23 (1 hour increments) (none)
13 MIN XX SET REAL TIME CLOCK MIN
Minute 0-59 (1 min. increments) (none)
14
M D Y
D M Y
SET REAL TIME DATE DISPLAY -
MONTH DAY YEAR OR
DAY MONTH YEAR
M D Y or D M Y
15 MP3K DIS INCOM COMMUNICATIONS MODE
Toggle between DIS or EN
MP3K EN - MP3000 EMULATION
MP3K DIS - MP4000 COMMUNICATION
16 RLYF TRP
RLYF ALM
or
RLYF T+A
INTERNAL DIAGNOSTIC FAILURE
ACTIVATES TRIP AND OR ALARM
RELAY
Toggles between RLYF TRP, RLYF ALM and
RLYF T+A
17 INCT DIS
or
INCT EN
INCOM TRIP DISABLED OR ENABLED
Toggles between INCT DIS and INCT EN
18 DISARMED
or
ARMED
ARM OR DISARM TRIP RELAY
WARNING DISARM WILL NOT ALLOW
TRIP RELAY TO FUNCTION
Toggles between ARMED and DISARMED
PAGE 13, SP TEST SETTINGS FOR TESTING INPUTS AND OUTPUTS
1 3 PHASE
or
1 PHASE
SINGLE PHASE TEST MODE OR
THREE PHASE PROTECTION MODE
Toggles between 3-PHASE and 1-PHASE
NOTE: 1-PHASE is for bench testing ONLY.