EasyManua.ls Logo

Eaton NFX9000 - Chapter 2: Power and Control Wiring; Basic Wiring

Eaton NFX9000
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
NFX9000 Adjustable Frequency Drives
MN04002003E
For more information visit: www.EatonElectrical.com
2-1
February 2006
Chapter 2 — Power and Control Wiring
Basic Wiring
Users must connect wiring according to the circuit diagram shown in Figure 2-1. Please
follow all national and state wiring codes when wiring the drive.
Figure 2-1: Basic Wiring
Note: Do not plug a modem or telephone line into the RS-485 communication port or
permanent damage may result. Terminals 1 and 2 are the power source for the optional
copy keypad and should not be used while using the RS-485 communication.
U/T1
6
1
RS-485
Communication
Port
RA
RC
Relay Output Contacts
120V AC/28V DC 3A
Factory Default: Fault Indication
Main Circuit
(Power) Terminals
1 :
+
EV
2 : GND
3 : SG
-
4 : SG
+
+
18V
Factory Default Settings
D1
4.7 KΩ
Forward/Stop
RJ-11
V/T2
Motor
W/T3
R/L1
S/L2
T/L3
R/L1
S/L2
T/L3
IM
3-Phase
Control Circuit
Terminals
Shielded Leads
+
18V
D2
4.7 KΩ
Reverse/Stop
+
18V
D3
4.7 KΩ
Reset
+
18V
D4
GND
4.7 KΩ
Multi-Step 1
Common Signal
Power Supply for Potentiometer
+
10V 10 mA (Max.)
+
10V
Master Freq. Setting
3
2
Analog Voltage
0 ~ 10V DC
Analog Current
4 ~ 20 mA
AVI
GND
1
VR
VR: 3 – 5
KΩ

Other manuals for Eaton NFX9000