For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
NFX9000 Adjustable Frequency Drives
MN04002003E
For more information visit: www.EatonElectrical.com
3-3
February 2006
Table 3-3: Group 2 — Operation Method Parameters
Table 3-4: Group 3 — Output Function Parameters
Code Parameter Min. Max. Unit Default Cust Note
2-00 Source of frequency
command
04 0 0: Digital keypad
1: 0 – 10V from AVI
2: 4 – 20 mA from AVI
3: Controlled by V.R. on drive
4: RS-485 communication interface
2-01 Source of operation
command
04 0 0: By digital keypad
1: By external terminals, keypad
STOP enable
2: By external terminals, keypad
STOP disable
3: By RS-485 communication
interface, keypad STOP enable
4: By RS-485 communication
interface, keypad STOP disable
2-02 Stop method 0 1 0 0: Ramp stop
1: Coast stop
2-03 Carrier frequency 3 10K Hz 10 3 – 10K Hz
2-04 Reverse operation
inhibit
02 0 0: Enable reverse
1: Disable reverse
2: Disable forward
2-05 ACI (4 – 20 mA) input
loss detection
02 0 0: Decelerate to 0 Hz
1: Stop immediately, display EF
2: Run with the last frequency
2-06 Line start lockout 0 1 0 0: Enable
1: Disable
Code Parameter Min. Max. Unit Default Cust Note
3-00 Desired frequency
attained
1.0 400 Hz 1.0 1.0 – 400 Hz
3-01 Terminal count value 0 999 0 0 – 999
3-02 Preliminary count
value
0 999 0 0 – 999
3-03 Multi-function relay
output
016 8 0: Not used
1: AC drive operational
2: Maximum output frequency
attained
3: Zero speed
4: Over torque
5: Base-block (B.B.)
6: Low voltage detection
7: AC drive operation mode
8: Fault indication
9: Desired frequency attained
10: PLC program running
11: PLC program step complete
12: PLC program complete
13: PLC program operation pause
14:
Terminal count value attained
15:
Preliminary count value attained
16: Ready state indicator