Table 3-2: Group 1 — Basic Parameters
The parameter may be set during operation.
Code Parameter Min. Max. Unit Default Cust Note
1-00 Maximum operation
frequency
50.0 400 Hz 60.0 50.0 – 400 Hz
1-01 Maximum voltage
frequency
10.0 400 Hz 60.0 10.0 – 400 Hz
1-02 Maximum output
voltage
2.0 255 V 220 2.0 – 255V
1-03 Mid-point frequency 1.0 400 Hz 1.0 1.0 – 400 Hz
1-04 Mid-point voltage 2.0 255 V 12.0 2.0 – 255V
1-05 Minimum output
frequency
1.0 60.0 Hz 1.0 1.0 – 60 Hz
1-06 Minimum output
voltage
2.0 255 V 12.0 2.0 – 255V
1-07 Upper bound of
frequency
1 110 % 100 1 – 110%
1-08 Lower bound of
frequency
0 100 % 0 0 – 100%
1-09
Acceleration time 1
(Tacc1)
0.1 600 sec. 10.0 0.1 – 600 seconds
1-10
Deceleration time 1
(Tdec1)
0.1 600 sec. 10.0 0.1 – 600 seconds
1-11
Acceleration time 2 0.1 600 sec. 10.0 0.1 – 600 seconds
1-12
Deceleration time 2 0.1 600 sec. 10.0 0.1 – 600 seconds
1-13
JOG acceleration time 0.1 600 sec. 10.0 0.1 – 600 seconds
1-14
JOG deceleration
time
0.0 600 sec. 10.0 0.0 – 600 seconds
1-15
JOG frequency 1.0 400 Hz 6.0 1.0 – 400 Hz
1-16 Auto acceleration/
deceleration
05 0 0: Linear accel./decel.
1: Auto accel., linear decel.
2: Linear accel., auto decel.
3: Auto accel./decel.
4: Linear accel., auto decel. (stall
prevention during deceleration
5: Auto accel./decel. (stall
prevention during deceleration)
1-17 S-curve setting in
acceleration
07 0 0 7
1-18 S-curve setting in
deceleration
07 0 0 7