Table 3-6: Group 5 — Multi-Step Speed and PLC Parameters
Table 3-7: Group 6 — Protection Parameters
Code Parameter Min. Max. Unit Default Cust Note
5-00 First step speed
frequency
0.0 400 Hz 0 0 – 400 Hz
5-01 Second step speed
frequency
0.0 400 Hz 0 0 – 400 Hz
5-02 Third step speed
frequency
0.0 400 Hz 0 0 – 400 Hz
5-03 PLC mode 0 4 0 0: Disable PLC operation
1: Execute one program cycle
2: Continuously execute program
cycles
3: Execute one program cycle
step by step (separate by
STOP)
4: Continuously execute one
program cycle step by step
(separate by STOP)
5-04 PLC forward/reverse
motion
0 1 0 0 – 15
0: Forward
1: Reverse
5-05 Time duration step 0 0 65500 sec. 0 0 – 65500 seconds
5-06 Time duration step 1 0 65500 sec. 0 0 – 65500 seconds
5-07 Time duration step 2 0 65500 sec. 0 0 – 65500 seconds
5-08 Time duration step 3 0 65500 sec. 0 0 – 65500 seconds
Code Parameter Min. Max. Unit Default Cust Note
6-00 Over-voltage
prevention level
0 410 V 390 0: Disable, 350 – 410V
6-01 Over-current
prevention level
0 200 % 170 0: Disable, 20 – 200%
6-02 Over-torque detection 0 4 0 0: Disable
1: Enabled during constant speed
operation; continues until the
continuous limit is reached
2: Enabled during constant speed
operation; halted after detection
3: Enabled during acceleration;
continues before continuous
output time limit is reached
4: Enabled during acceleration;
halted after over-torque detection
6-03 Over-torque detection
level
30 200 % 150 30 – 200%
6-04 Over-torque detection
time
0.1 10.0 sec. 0.1 0.1 – 10.0 seconds