NFX9000 Adjustable Frequency Drives
MN04002003E
For more information visit: www.EatonElectrical.com
3-1
February 2006
Chapter 3 — Parameters
Parameter Lists
Table 3-1: Group 0 — User Parameters
The parameter may be set during operation.
Code Parameter Min. Max. Unit Default Cust Note
0-00 Identity code of
drive (read only)
16 1: 40W
2: 100W
3: 200W
4: 400W
5: 750W
6: 1.5 kW
0-01 Rated current
display (read only)
— — 40W: .4A
100W: .8A
200W: 1.6A
400W: 2.5A
750W: 4.2A
1.5 kW: 7.0A
0-02 Parameter reset 0 10: Reset parameters to factory
setting
0-03
Start-up display of
drive
03 0 0: F (frequency command)
1: H (output frequency)
2: U (user-defined unit)
3: A (output current)
0-04
User-defined unit 0 4 0 0: Display user-defined unit (u)
1: Display counter value (C)
2: Display process operation (1=tt)
3: Display DC bus voltage (U)
4: Display output voltage (E)
0-05
User-defined
coefficient (K)
0.1 160 1.0 0.1 – 160
0-06 Software version — — #.# Read only
0-07 Password input 0 999 0 0 – 999
0-08 Password
configuration
0 999 0 0 – 999