NFX9000 Adjustable Frequency Drives
3-6
For more information visit: www.EatonElectrical.com
MN04002003E
February 2006
Table 3-7: Group 6 — Protection Parameters, continued
Code Parameter Min. Max. Unit Default Cust Note
6-05 Electronic thermal
overload relay
02 0 0: Not used
1: Act with standard motor
2: Act with special motor
6-06 Electronic thermal
characteristic
30 600 sec. 60 30 – 600 seconds
6-07 Present fault record 0 11 0 0: No fault occurred
1: oc (over-current)
2: ov (over-voltage)
3: oH (overheat)
4: oL (overload)
5: oL1 (electronic thermal)
6: EF (external fault)
7: Reserved
8: Reserved
9: ocA (current exceed during
acceleration)
10: ocd (current exceed during
deceleration)
11: ocn (current exceed during
steady state)
12: Reserved
13: Reserved
14: Reserved
15: CPU failure 1 (cF1)
16: CPU failure 2 (cF2)
17: Reserved
18: Overload (oL2)
19: Auto acc/dec failure (cFA)
20: Software protection enabled
(code)
21: Reserved
22: CPU failure (cF3.1)
23: CPU failure (cF3.2)
24: CPU failure (cF3.3)
25: CPU failure (cF3.4)
26: CPU failure (cF3.5)
27: CPU failure (cF3.6)
28: CPU failure (cF3.7)
29: Hardware protection failure
(HPF.1)
30: Hardware protection failure
(HPF.2)
31: Hardware protection failure
(HPF.3)
6-08 Second most recent
fault record
0 11 0 Same as 6-07
6-09 Third most recent fault
record
0 11 0 Same as 6-07
6-10 Fourth most recent
fault record
0 11 0 Same as 6-07
6-11 Fifth most recent fault
record
0 11 0 Same as 6-07
6-12 Sixth most recent fault
record
0 11 0 Same as 6-07