Loading...
IO21 x AI, 2 x AO Option Card
PowerXL DG1 Series Option Cards MN040007EN—April 2014 www.eaton.com 19
IO2 Board Parameters
Parameters are all listed in the Optional board menu for this
card.
Figure 15. IO2 Parameter Structure
Table 13. IO2 Board Parameters
Monitor Menu—BX.1
Code Parameter Min. Max. Default Unit ID (Slot A / Slot B) Description R / RW
BX.1.1 AI1 Value 894 / 920 Analog Input Status R
BX.1.2 AO1 Value 897 / 922 Analog Output Status R
BX.1.3 AO2 Value 899 / 924 Analog Output Status R
Parameter Menu—BX.2
Code Parameter Min. Max. Default Unit ID (Slot A / Slot B) Description R / RW
BX.2.1 AI1 Mode 0 2 0 893 / 919 Analog input 1 Mode
0: 0 to 20 mA
1: 0 to 10V
2: –10V to +10V
RW
BX.2.2 AI1 Range 0 2 0 124 / 129 Analog input 1 signal range
0: 0 to 100%
1: 20 to 100%
2: Customized
RW
BX.2.3 AI1 Custom Min 0 100 0 % 125 / 130 Analog input 1 custom minimum range RW
BX.2.4 AI1 Custom Max 0 100 100 126 / 131 Analog input 1 custom maximum range RW
BX.2.5 AI1 Filter Time 0 10 0.1 s 123 / 128 Analog input 1 filter time RW
BX.2.6 AI1 Invert 0 1 0 127 / 132 Analog input 1 signal inversion
0: Not Inverted
1: Inverted
RW
BX.2.7 AO1 Mode 0 1 0 896 / 922 Analog output mode
0: 0 to 20 mA
1: 0 to 10V
RW
BX.2.8 AO1 Function 0 235 / 275 Analog output 1 function RW
BX.2.9 AO1 Min 0 1 0 238 / 276 Analog output minimum value
0: 0V / 0 mA
1: 2V / 4 mA default 0V / 0 mA
RW
BX.2.10 AO1 Filter Time 0 10 1 s 236 / 277 Analog output filter time range RW
BX.2.11 AO1 Scale 0 100 100 % 239 / 278 Analog output 1 scale RW